<?xml version="1.0" encoding="UTF-8"?><!DOCTYPE article  PUBLIC "-//NLM//DTD Journal Publishing DTD v3.0 20080202//EN" "http://dtd.nlm.nih.gov/publishing/3.0/journalpublishing3.dtd"><article xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink" dtd-version="3.0" xml:lang="en" article-type="research article"><front><journal-meta><journal-id journal-id-type="publisher-id">JECTC</journal-id><journal-title-group><journal-title>Journal of Electronics Cooling and Thermal Control</journal-title></journal-title-group><issn pub-type="epub">2162-6162</issn><publisher><publisher-name>Scientific Research Publishing</publisher-name></publisher></journal-meta><article-meta><article-id pub-id-type="doi">10.4236/jectc.2013.34014</article-id><article-id pub-id-type="publisher-id">JECTC-40534</article-id><article-categories><subj-group subj-group-type="heading"><subject>Articles</subject></subj-group><subj-group subj-group-type="Discipline-v2"><subject>Engineering</subject><subject> Physics&amp;Mathematics</subject></subj-group></article-categories><title-group><article-title>
 
 
  Effect of Non-Condensable Gas Leakage on Long Term Cooling Performance of Loop Thermosyphon
 
</article-title></title-group><contrib-group><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>iroyuki</surname><given-names>Toyoda</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref><xref ref-type="corresp" rid="cor1"><sup>*</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Yoshihiro</surname><given-names>Kondo</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref></contrib></contrib-group><aff id="aff1"><addr-line>Hitachi Research Laboratory, Hitachi, Ltd., 832-1 Horiguchi, Hitachinaka, Ibaraki, Japan</addr-line></aff><author-notes><corresp id="cor1">* E-mail:<email>hiroyuki.toyoda.qr@hitachi.com(IT)</email>;</corresp></author-notes><pub-date pub-type="epub"><day>06</day><month>12</month><year>2013</year></pub-date><volume>03</volume><issue>04</issue><fpage>131</fpage><lpage>135</lpage><history><date date-type="received"><day>August</day>	<month>29,</month>	<year>2013</year></date><date date-type="rev-recd"><day>September</day>	<month>30,</month>	<year>2013</year>	</date><date date-type="accepted"><day>October</day>	<month>8,</month>	<year>2013</year></date></history><permissions><copyright-statement>&#169; Copyright  2014 by authors and Scientific Research Publishing Inc. </copyright-statement><copyright-year>2014</copyright-year><license><license-p>This work is licensed under the Creative Commons Attribution International License (CC BY). http://creativecommons.org/licenses/by/4.0/</license-p></license></permissions><abstract><p>
 
 
  We have developed a loop thermosyphon for cooling electronic devices. The cooling performance of a thermosyphon deteriorates with an increasing amount of non-condensable gas (NCG). Design of a thermosyphon must consider NCG to provide guaranteed performance for a long time. In this study, the heat transfer performance of a thermosyphon was measured while changing the amount of NCG. The resultant performances were expressed as approximations. These approximations enabled us to predict the total thermal resistance of the thermosyphon by the amount of NCG and input heating. Then, using the known leakage in the thermosyphon and the amount of dissolved NCG in the water, we can predict the amount of NCG and the total thermal resistance of the thermosyphon after ten years. Although there is a slight leakage in the thermosyphon, we are able to design a thermosyphon with a guaranteed level of cooling performance for a long time using the proposed design method.
 
</p></abstract><kwd-group><kwd>Thermosyphon; Boiling; Condensation; Non-Condensable Gas; Heat Transfer Performance; CPU Cooling</kwd></kwd-group></article-meta></front><body><sec id="s1"><title>1. Introduction</title><p>Electronic devices need to be more compact these days, but it has become difficult to cool them sufficiently with existing air cooling systems that use only heat conductivity. We have developed a loop thermosyphon to provide high cooling performance for electronic devices [1,2]. The thermosyphon has some important features. One is that it has a porous structure that enhances evaporative heat transfer for the evaporation section to decrease thermal resistance. Another is that the position of the radiator can be freely adjusted by extending the joint pipes. This is highly beneficial when designing the server cooling system. Cooling systems for highly reliable electronic devices like servers must offer guaranteed performance for more than 10 years. However, the thermosyphon’s cooling performance deteriorates with an increasing amount of non-condensable gas (NCG) [<xref ref-type="bibr" rid="scirp.40534-ref3">3</xref>]. Although the container of our thermosyphon is sealed tightly, a helium leak detector cannot detect leakages below 10<sup>−10</sup> Pa-m<sup>3</sup>/s. This value represents a typical small leakage. However, over a period of 10 years, a large amount of gas will leak and build up in the thermosyphon.</p><p>There has been a lot of research on cooling systems for electronic devices. Naphon et al. [<xref ref-type="bibr" rid="scirp.40534-ref4">4</xref>] studied a nanofluid jet impingement cooling system. Mohamed et al. [<xref ref-type="bibr" rid="scirp.40534-ref5">5</xref>] studied a mini-channel heat sink in electronic devices. Webb et al. [<xref ref-type="bibr" rid="scirp.40534-ref6">6</xref>] studied a thermosyphon using a sintered boiling surface and louver fins to cool desktop computers to dissipate 100 W. Their working fluid was R-134A and water. Samba et al. [<xref ref-type="bibr" rid="scirp.40534-ref7">7</xref>] reported on thermal performance of a loop thermosyphon for cooling telecommunication equipment to dissipate 600 W. Their working fluid was n-pentane. However, we cannot find research on the aged deterioration of a thermosyphon based on the amount of leaked NCG. It is industrially important to take the effect of such leakage on the performance into account when designing the thermosyphon.</p><p>In this study, the effect of the amount of NCG on heat transfer performance of the loop thermosyphon was investigated. Then, the amount of NCG flowing into the thermosyphon and the change in long term heat transfer performance after 10 years were predicted. We propose a design method of a thermosyphon with a guaranteed level of cooling performance for a long time.</p></sec><sec id="s2"><title>2. Loop Thermosyphon Experimental Apparatus</title><p>We have developed a loop thermosyphon to provide high cooling performance for electronic devices [1,2]. Figures 1 and 2 show the thermosyphon. As the choice of refrigerant is environmentally important, we used degassed water. The thermosyphon was made of copper to resist corrosion by water. For the evaporation section, we used a porous structure for the evaporation surface. The evaporation surface was attached to the object to be cooled by evaporation. The vapor generated by evaporation flowed along the vapor tube (the larger upper tube in <xref ref-type="fig" rid="fig2">Figure 2</xref>) and then flowed into the condenser. The condensation section was 35.5 mm long and was made by flattening a circular tube with an inner diameter of 11.1 mm. This tube has microgrooves inside. The condensation section has offset fins attached to the outside of the condensation tube. The vapor flowing from the evaporation section was condensed into water in the condensation tube, and the heat from the object being cooled was dissipated into the airflow through the offset fins. The water that condensed in the condensation tube flowed into the evaporation section through the water tube (the lower tube in <xref ref-type="fig" rid="fig2">Figure 2</xref>). The thermosyphon cools the object by repeating this cycle. In <xref ref-type="fig" rid="fig2">Figure 2</xref>, the thin tube attached to the evaporation chamber, called the injection tube, is used to create a vacuum and to inject water. The injection tube is sealed tightly after water has been injected.</p><p>We measured the thermosyphon’s cooling performance while changing the amount of input heating, the flow rate of the cooling air, and the amount of NCG. As shown in <xref ref-type="fig" rid="fig1">Figure 1</xref>, we attached a heater (a ceramic heater 25 mm &#215; 25 mm and 1.8 mm thick) to the evaporation surface with thermal grease. We measured the power consumption of this heater by using the inputted electric current and voltage and took this as the amount of input heating Q. We thought that it was important to be able to predict thermal performance easily based on the calorific value of the object to be cooled like the CPU (central</p><p>processing unit) in a server. Thus, the following performance experiments were performed based on the amount of input heating. Moreover, to examine the thermosyphon in the same conditions as actual use conditions, there was no thermal insulation on the thermosyphon’s surface. Three amounts of input heating were tested in this experiment: Q = 50, 100, and 200 W. A uniform cooling air flow into the condenser was obtained from a double chamber wind tunnel. Flow rates of U = 0.3, 0.5, and 0.9 m<sup>3</sup>/min. were used. The temperature measuring points are shown in <xref ref-type="fig" rid="fig1">Figure 1</xref>, where T<sub>h</sub> is the temperature of the heater, T<sub>e</sub> is the temperature of the evaporation plate center, T<sub>v</sub> is the temperature of the vapor (we assume the vapor tube surface temperature is the same as the vapor temperature), and T<sub>a-in</sub> is the temperature of the cooling air in front of the condenser. We divided the measuring areas of the condensation tube equally into three and measured the temperatures in these condensation tube regions, T<sub>c-up</sub> (upper area), T<sub>c-mid</sub> (middle area), and T<sub>c-low</sub> (lower area). Moreover, we measured the exhaust air flow temperatures, T<sub>a-up</sub>, T<sub>a-mid</sub>, and T<sub>a-low</sub>, corresponding to these regions. To simplify the comparison, we used the mean temperature of the condensation tube T<sub>c</sub> and the mean exhaust air flow temperature T<sub>a-out</sub>.</p></sec><sec id="s3"><title>3. Cooling Performance Experimental Results</title><p>We evaluated the thermosyphon’s cooling performance by dividing it into three regions: one for evaporation performance, the second for condensation performance in the condensation tube and air cooling performance at the condenser, and the third for the heat leakage from the outside surface of the thermosyphon. Finally, the total thermal resistance of the thermosyphon was discussed.</p><sec id="s3_1"><title>3.1. Evaporation Performance</title><p>We evaluated the evaporation heat transfer coefficient of the evaporation surface. The evaporation heat transfer coefficient was defined by the following equation.</p><disp-formula id="scirp.40534-formula1148"><label>(1)</label><graphic position="anchor" xlink:href="1-1520034\b9b9e3bb-fe38-49c6-b485-29521127a3ea.jpg"  xlink:type="simple"/></disp-formula><p>Here, S<sub>e</sub> is the porous surface area of the evaporation surface (S<sub>e</sub> = 1.51 &#215; 10<sup>−3 m2</sup>), Q is the input heating, T<sub>v</sub> is the vapor temperature, and T<sub>e</sub> is the evaporation surface temperature. The experimental results of the evaporation heat transfer coefficient are shown in <xref ref-type="fig" rid="fig3">Figure 3</xref>. The total pressure in the thermosyphon P<sub>0</sub> was defined as P<sub>0</sub> = P<sub>NCG</sub> + P<sub>v</sub>. Here, P<sub>NCG</sub> is the partial pressure of NCG, and P<sub>v</sub> is the pressure of saturated vapor, which is given by the temperature of vapor T<sub>V</sub>. The dashed line in <xref ref-type="fig" rid="fig3">Figure 3</xref> shows the calculation result of the correlation equation of the pool boiling heat transfer coefficient on the flat surface in the saturated conditions proposed by Kutateladze [<xref ref-type="bibr" rid="scirp.40534-ref8">8</xref>]. The evaporation heat transfer of our porous structure is about five times as large as that of the flat surface. We obtained an expression of the approximation from the evaporation heat transfer coefficient h<sub>e</sub>, the pressure P<sub>0</sub>, and the heat flux of the evaporation surface q = Q/S<sub>e </sub>, by using the least squares method.</p><disp-formula id="scirp.40534-formula1149"><label>(2)</label><graphic position="anchor" xlink:href="1-1520034\d5fc6909-3722-4ee9-9e66-27416ea7ce3b.jpg"  xlink:type="simple"/></disp-formula></sec><sec id="s3_2"><title>3.2. Cooling Performance of Condensation Section</title><p>We evaluated the condensation performance in the condenser tube. The amount of input heating Q and the condensation heat transfer rate Q<sub>cond</sub> are different because of the heat leakage from the thermosyphon. Therefore we measured the condensation heat transfer rate Q<sub>cond</sub> by using the temperature increase of the cooling air (T<sub>a-out</sub>- T<sub>a-in</sub>). The total condensation heat transfer coefficient h<sub>c-total</sub> was defined by the following equation.</p><disp-formula id="scirp.40534-formula1150"><label>(3)</label><graphic position="anchor" xlink:href="1-1520034\df77a610-832c-437f-a4a1-78ccb45ab9c3.jpg"  xlink:type="simple"/></disp-formula><p>Here, S<sub>c</sub> is the total area of the inner condensation tube surface (S<sub>c</sub> = 4.95 &#215; 10<sup>−3 m2</sup>), T<sub>v</sub> is the vapor temperature, and T<sub>c</sub> is the mean temperature of the condensation tube. The relation between the condensation heat transfer coefficient and the partial pressure of NCG is shown in <xref ref-type="fig" rid="fig4">Figure 4</xref> for three amount of the input heating Q. The condensation heat transfer coefficient decreased drastically when the partial pressure of NCG increased. We obtained an expression of the approximation from the condensation heat transfer coefficient h<sub>c-total</sub>, the partial pressure of NCG (P<sub>NCG</sub>), and the condensation heat transfer rate<img src="1-1520034\8b9a3536-0c4b-4407-89df-98e1551b8284.jpg" />, by using the least squares method.</p><disp-formula id="scirp.40534-formula1151"><label>(4)</label><graphic position="anchor" xlink:href="1-1520034\e12ddb7a-ca35-46e7-a514-915dc999ef30.jpg"  xlink:type="simple"/></disp-formula><p>The approximation is shown with solid lines in <xref ref-type="fig" rid="fig4">Figure 4</xref>, and the difference between the experimental results and the approximation is 25% - 41%.</p><p>Next, we evaluated the air cooling performance on the outside of the condenser tube. The condenser has offset fins attached to the outside of the condensation tube. The forced convection heat transfer coefficient h<sub>f</sub> on the offset fins was obtained from the following equation.</p><disp-formula id="scirp.40534-formula1152"><label>(5)</label><graphic position="anchor" xlink:href="1-1520034\ef7f43ea-517b-40a3-a594-25da0adf4704.jpg"  xlink:type="simple"/></disp-formula><p>Here, S<sub>fin</sub> is the total area of the offset fins, T<sub>c</sub> is the mean temperature of the condensation tube, and T<sub>a-in</sub> is the temperature of the cooling air in front of the condenser. Manglik et al. [<xref ref-type="bibr" rid="scirp.40534-ref9">9</xref>] reported on an experimental formula for the forced convection heat transfer coefficient for the offset fins. The calculation and experimental results of the heat transfer coefficient h<sub>f</sub> on offset fins for different air flow rates U are shown in <xref ref-type="fig" rid="fig5">Figure 5</xref>. The difference between the experimental results and the calculation is 14.2%.</p></sec><sec id="s3_3"><title>3.3. Heat Leakage from Thermosyphon</title><p>The condensation heat transfer Q<sub>cond</sub> is less than amount of the input heating Q because of heat leakage from the thermosyphon. The fraction of this difference was 0% - 8% when the NCG pressure was 0 - 1 kPa and 10% - 19% when the NCG pressure was 1 - 5.5 kPa. We obtained an expression of the approximation of the heat leakage (Q-Q<sub>cond</sub>) as a function of the temperature difference of the vapor temperature, the cooling air temperature (T<sub>v</sub>-T<sub>a-in</sub>), and the air flow rate U from our experimental data by the following equation.</p><disp-formula id="scirp.40534-formula1153"><label>(6)</label><graphic position="anchor" xlink:href="1-1520034\e2bd2908-5996-4012-9005-b8d789c04168.jpg"  xlink:type="simple"/></disp-formula></sec><sec id="s3_4"><title>3.4. Total Thermal Resistance of Thermosyphon</title><p>The total thermal resistance θ of the thermosyphon is defined by the following equation.</p><disp-formula id="scirp.40534-formula1154"><label>(7)</label><graphic position="anchor" xlink:href="1-1520034\00a75a8a-a26a-408a-bc5e-44d62e9f0234.jpg"  xlink:type="simple"/></disp-formula><p>Here, Q is the amount of input heating, T<sub>e</sub> is the evaporation surface temperature, and T<sub>a-in</sub> is temperature of the cooling air in front of the condenser. Using the abovementioned approximations, we can predict the total thermal resistance θ of the thermosyphon for given values of the partial pressure of NCG (P<sub>NCG</sub>), the amount of input heating Q, the temperature of the cooling air in front of the condenser T<sub>a-in</sub>, and the air flow rate U. The predicted and experimental results of the total thermal resistance of the thermosyphon for the air flow rate U = 0.008 m<sup>3</sup>/s are shown in <xref ref-type="fig" rid="fig6">Figure 6</xref>. The difference between the experimental results and the prediction is 8% - 17%, which is good enough for the design of the thermosyphon.</p></sec></sec><sec id="s4"><title>4. Long Term Change of Cooling Performance Due to NCG Leakage</title><p>Here, by using the above-mentioned results, the thermal design approach for thermosyphons with slight NCG leakage is shown as follows. First, we predict the amount of partial pressure of NCG (P<sub>NCG</sub>) in the thermosyphon after 10 years with a constant leakage rate r<sub>leak</sub> and amount of dissolved NCG in injected water (DO). The leakage rate r<sub>leak</sub> gives the amount of molecules that flow into the thermosyphon when the inside is a vacuum and the outside pressure is atmospheric pressure P<sub>a</sub>. Assuming that the leakage rate is proportional to the difference between the inner pressure P<sub>0</sub> and the external pressure P<sub>a</sub>, the following expression is obtained.</p><disp-formula id="scirp.40534-formula1155"><label>(8)</label><graphic position="anchor" xlink:href="1-1520034\bcb18efe-2e92-4872-ab86-cb0ad8e73087.jpg"  xlink:type="simple"/></disp-formula><p>Therefore, the inner pressure of the thermosyphon after t seconds is given by the following equation.</p><disp-formula id="scirp.40534-formula1156"><label>(9)</label><graphic position="anchor" xlink:href="1-1520034\83d6af31-102e-4dd5-bb16-d66b4325a560.jpg"  xlink:type="simple"/></disp-formula><p>Here, P<sub>d</sub> is the initial partial pressure of the dissolved NCG in injected water, and P<sub>v</sub> is the saturation vapor pressure at 25˚C. The calculation result of the amount of partial pressure of NCG (P<sub>NCG</sub>) is shown in <xref ref-type="fig" rid="fig7">Figure 7</xref>. The amount of dissolved NCG in injected water (DO) in <xref ref-type="fig" rid="fig7">Figure 7</xref> means the amount of dissolved oxygen in water before injection into the thermosyphon. Also, we assumed that the amount of the dissolved nitrogen was twice that of dissolved oxygen. It was assumed that all the dissolved gases were discharged into the thermosyphon, and we predicted the amount of NCG discharged from the injected water.</p><p>Using Figures 6 and 7, we can predict the change in cooling performance of a thermosyphon with NCG leakage. <xref ref-type="fig" rid="fig8">Figure 8</xref> shows three examples of the relation between the total thermal resistance and the elapsed years for the amount of heat input heating Q = 100 W. For the situation A (the leak rate r<sub>leak</sub> = 3 &#215; 10<sup>−9</sup> Pa-m<sup>3</sup>/s, dissolved oxygen DO = 2 mg/L, and air flow rate U = 0.008</p><p>m<sup>3</sup>/s), the total thermal resistance θ was over 0.25 K/W after 10 years. The total thermal resistance after 10 years increased by 25% of the initial value. When the dissolved oxygen DO = 0 mg/L as in situation B, the total thermal resistance θ was less than 0.25 K/W after 10 years. When the air flow rate U = 0.015 m<sup>3</sup>/s in situation C, the total thermal resistance θ was also less than 0.25 K/W after 10 years. We proposed a new design method for a thermosyphon with a guaranteed level of cooling performance for a long time.</p></sec><sec id="s5"><title>5. Conclusions</title><p>We measured the heat transfer performance of a loop thermosyphon with non-condensable gas (NCG), and the resultant performances were expressed as approximations. Then, we proposed a design method for a thermosyphon with a guaranteed level of cooling performance for a long time. We obtained the following results:</p><p>1) The predicted total thermal resistance of the thermosyphon using the obtained approximations agreed with the experimental results within an error of 8% - 17%.</p><p>2) The total thermal resistance of the thermosyphon increased by 25% after 10 years when leakage rate r<sub>leak</sub> = 3&#215;10<sup>−9</sup> Pa-m<sup>3</sup>/s, dissolved oxygen DO = 2 mg/L, and air flow rate U = 0.008 m<sup>3</sup>/s.</p><p>3) Although there was a slight leakage in the thermo syphon, we were able to design a thermosyphon with a guaranteed level of cooling performance for a long time using the proposed design method.</p></sec><sec id="s6"><title>REFERENCES</title></sec><sec id="s7"><title>NOTES</title></sec></body><back><ref-list><title>References</title><ref id="scirp.40534-ref1"><label>1</label><mixed-citation publication-type="other" xlink:type="simple">H. Toyoda, T. Nakajima, Y. Kondo, A. Idei and S. Sato, “A Design for Loop Thermosyphon including Effect of Non-Condensable Gas,” Proceedings of ASME/JSME 2011 8th Thermal Engineering Joint Conference, AJTEC2011- 44244, 2011.</mixed-citation></ref><ref id="scirp.40534-ref2"><label>2</label><mixed-citation publication-type="other" xlink:type="simple">H. Toyoda, Y. Kondo, S. Sato and S. Tsubaki, “Effects of Non-Condensable Gases on Heat Transfer Performance of Loop Thermosyphon for CPU Cooling,” Transactions of Japan Society of Mechanical Engineers, Series B, Vol. 8, No. 759, 2012, pp. 2030-2045 (in Japanese).  
http://dx.doi.org/10.1299/kikaib.78.2030</mixed-citation></ref><ref id="scirp.40534-ref3"><label>3</label><mixed-citation publication-type="other" xlink:type="simple">V. Dube, A. Akbarzadeh and J. Andrews, “The Effects of Non-Condensable Gases on the Performance of Loop Thermosyphon Heat Exchangers,” Applied Thermal Engineering, Vol. 24, No. 16, 2004, pp. 2439-2451.  
http://dx.doi.org/10.1016/j.applthermaleng.2004.02.013</mixed-citation></ref><ref id="scirp.40534-ref4"><label>4</label><mixed-citation publication-type="other" xlink:type="simple">P. Naphon and S. Wongwises, “Experimental Study of Jet Nanofluids Impingement System for Cooling Computer Processing Unit,” Journal of Electronics Cooling and Thermal Control, Vol. 2, No. 3, 2011, pp. 38-44.  
http://dx.doi.org/10.4236/jectc.2011.13005</mixed-citation></ref><ref id="scirp.40534-ref5"><label>5</label><mixed-citation publication-type="other" xlink:type="simple">M. M. Mohamed and M. A. A. El-Baky, “Air Cooling of Mini-Channel Heat Sink in Electronic Devices,” Journal of Electronics Cooling and Thermal Control, Vol. 3, No. 2, 2013, pp. 49-57.  
http://dx.doi.org/10.4236/jectc.2013.32007</mixed-citation></ref><ref id="scirp.40534-ref6"><label>6</label><mixed-citation publication-type="other" xlink:type="simple">R. L. Webb and S. Yamauchi, “Test Results on a Thermo-Syphon Concept to High-Power Cool Desktop Computers and Servers,” Proceedings of 18th IEEE SEMI-THERM Symposium, 2002, pp. 151-158.</mixed-citation></ref><ref id="scirp.40534-ref7"><label>7</label><mixed-citation publication-type="other" xlink:type="simple">A. Samba, H. L. Gualous, S. L. Masson and D. Norterhauser, “Two-Phase Thermosyphon Loop for Cooling Out-Door Telecommunication Equipments,” Applied Thermal Engineering, Vol. 50, No. 1, 2013, pp. 1351-1360.  
http://dx.doi.org/10.1016/j.applthermaleng.2012.05.023</mixed-citation></ref><ref id="scirp.40534-ref8"><label>8</label><mixed-citation publication-type="other" xlink:type="simple">S. S. Kutateladze, “US AEC Rep., AEC-tr-3770,” 1952.</mixed-citation></ref><ref id="scirp.40534-ref9"><label>9</label><mixed-citation publication-type="other" xlink:type="simple">R. M. Manglik and A. E. Bergles, “Heat Transfer and Pressure Drop Correlations for the Rectangular Offset Strip Fin Compact Heat Exchanger,” Experimental Thermal and Fluid Science, Vol. 10, No. 2, 1995, pp. 171-180.  
http://dx.doi.org/10.1016/0894-1777(94)00096-Q</mixed-citation></ref></ref-list></back></article>