<?xml version="1.0" encoding="UTF-8"?><!DOCTYPE article  PUBLIC "-//NLM//DTD Journal Publishing DTD v3.0 20080202//EN" "http://dtd.nlm.nih.gov/publishing/3.0/journalpublishing3.dtd"><article xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink" dtd-version="3.0" xml:lang="en" article-type="research article"><front><journal-meta><journal-id journal-id-type="publisher-id">JPEE</journal-id><journal-title-group><journal-title>Journal of Power and Energy Engineering</journal-title></journal-title-group><issn pub-type="epub">2327-588X</issn><publisher><publisher-name>Scientific Research Publishing</publisher-name></publisher></journal-meta><article-meta><article-id pub-id-type="doi">10.4236/jpee.2024.125003</article-id><article-id pub-id-type="publisher-id">JPEE-133663</article-id><article-categories><subj-group subj-group-type="heading"><subject>Articles</subject></subj-group><subj-group subj-group-type="Discipline-v2"><subject>Engineering</subject></subj-group></article-categories><title-group><article-title>
 
 
  Mitigation of Transients in Capacitor Coupled Substations Using Traditional RLC Filter Techniques
 
</article-title></title-group><contrib-group><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Sinqobile</surname><given-names>Wiseman Nene</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Bolanle</surname><given-names>Tolulope Abe</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Agha</surname><given-names>Francis Nnachi</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref></contrib></contrib-group><aff id="aff1"><addr-line>Department of Electrical Engineering, Tshwane University of Technology, eMalahleni, South Africa</addr-line></aff><pub-date pub-type="epub"><day>28</day><month>05</month><year>2024</year></pub-date><volume>12</volume><issue>05</issue><fpage>60</fpage><lpage>75</lpage><history><date date-type="received"><day>10,</day>	<month>April</month>	<year>2024</year></date><date date-type="rev-recd"><day>28,</day>	<month>May</month>	<year>2024</year>	</date><date date-type="accepted"><day>31,</day>	<month>May</month>	<year>2024</year></date></history><permissions><copyright-statement>&#169; Copyright  2014 by authors and Scientific Research Publishing Inc. </copyright-statement><copyright-year>2014</copyright-year><license><license-p>This work is licensed under the Creative Commons Attribution International License (CC BY). http://creativecommons.org/licenses/by/4.0/</license-p></license></permissions><abstract><p>
 
 
  This article presents an extensive examination and modeling of Capacitor Coupled Substations (CCS), noting some of their inherent constraints. The underlying implementation of a CCS is to supply electricity directly from high-voltage (HV) transmission lines to low-voltage (LV) consumers through coupling capacitors and is said to be cost-effective as compared to conventional distribution networks. However, the functionality of such substations is susceptible to various transient phenomena, including ferroresonance and overvoltage occurrences. To address these challenges, the study uses simulations to evaluate the effectiveness of conventional resistor-inductor-capacitor (RLC) filter in mitigating hazardous overvoltage resulting from transients. The proposed methodology entails using standard RLC filter to suppress transients and its associated overvoltage risks. Through a series of MATLAB/Simulink simulations, the research emphasizes the practical effectiveness of this technique. The study examines the impact of transients under varied operational scenarios, including no-load switching conditions, temporary short-circuits, and load on/off events. The primary aim of the article is to assess the viability of using an established technology to manage system instabilities upon the energization of a CCS under no-load circumstances or in case of a short-circuit fault occurring on the primary side of the CCS distribution transformer. The findings underscore the effectiveness of conventional RLC filters in suppressing transients induced by the CCS no-load switching.
 
</p></abstract><kwd-group><kwd>Capacitor Coupled Substation</kwd><kwd> System Modeling</kwd><kwd> Ferroresonance</kwd><kwd> RLC filters</kwd><kwd> Power Electronics</kwd><kwd> Transients</kwd><kwd> Capacitor Voltage Transformers</kwd><kwd> Transmission Lines</kwd></kwd-group></article-meta></front><body><sec id="s1"><title>1. Introduction</title><p>The foundational concepts of Capacitor Coupled Substations (CCS) have been firmly established and extensively explored in recent years [<xref ref-type="bibr" rid="scirp.133663-ref1">1</xref>] [<xref ref-type="bibr" rid="scirp.133663-ref2">2</xref>] [<xref ref-type="bibr" rid="scirp.133663-ref3">3</xref>] . The core operational principle of a CCS is based on traditional capacitor voltage transformers (CVT), commonly used for measurement and protective functions within power utility systems [<xref ref-type="bibr" rid="scirp.133663-ref4">4</xref>] . A CVT employs a capacitor divider to reduce transmission HV to levels suitable for measurement [<xref ref-type="bibr" rid="scirp.133663-ref5">5</xref>] . Although the capacitor divider concept has been recognized for some time, its recent application in transforming high voltage (HV) to medium voltage (MV) for power delivery has brought new challenges [<xref ref-type="bibr" rid="scirp.133663-ref6">6</xref>] . Designing a CCS requires addressing phenomena like transients and ferroresonance, which historically posed challenges in substation design. Ferroresonance in electric circuits occurs when a nonlinear inductance circuit is supplied from a source with series capacitance and the circuit subjected to disturbances caused by the opening and closing of the system circuit breakers [<xref ref-type="bibr" rid="scirp.133663-ref7">7</xref>] [<xref ref-type="bibr" rid="scirp.133663-ref8">8</xref>] . Ferroresonance can also be defined as a complex nonlinear electrical phenomenon that can lead to thermal and insulation failures in transmission and distribution systems [<xref ref-type="bibr" rid="scirp.133663-ref9">9</xref>] [<xref ref-type="bibr" rid="scirp.133663-ref10">10</xref>] . This phenomenon may result in overvoltage and over current which may result in the power system network components damage [<xref ref-type="bibr" rid="scirp.133663-ref11">11</xref>] .</p><p>A CCS is designed to directly supply electricity from HV transmission lines to MV systems, which is said to offer substantial cost advantages over conventional distribution networks. However, transient issues such as ferroresonance and overvoltage can cause damages in these substations [<xref ref-type="bibr" rid="scirp.133663-ref12">12</xref>] . This study focuses on the impact of transients during the specifically selected operating conditions.</p><p>The objective of this article is to develop a capacitor coupled substation integrating an efficient method to mitigate transients using conventional RLC filters. This objective is realized through the integration of conventional ferroresonance suppression circuit (FSC) on the secondary side of the CCS distribution transformer. The system is modelled and simulated on MATLAB/Simulink under no-load switching, ON and OFF switching and short-circuit fault applied to the primary side of the distribution transformer. The details of the model and simulation are detailed in the sections that follow. This study contributes to the knowledge body of the CCS behaviour during specific operations in order to understand and/or determine the impact on the downstream of the CCS.</p></sec><sec id="s2"><title>2. Background Theory</title><p>The ferroresonance phenomenon involves multiple modes with different frequencies, such as the fundamental frequency, sub-harmonic, quasi-periodic, and chaotic modes [<xref ref-type="bibr" rid="scirp.133663-ref13">13</xref>] . When a sudden transition between steady states occurs due to disturbances, switching actions, or gradual shifts in parameter values, ferroresonance can trigger overvoltage and overcurrent in power networks, posing a risk of damage to transformers and significant harm to network devices such as series capacitors [<xref ref-type="bibr" rid="scirp.133663-ref14">14</xref>] . Unlike resonance in circuits with linear capacitances and inductances, ferroresonance mainly occurs in circuits with nonlinear inductance due to the transformer core behaviour [<xref ref-type="bibr" rid="scirp.133663-ref15">15</xref>] . The magnetic core of the transformer is considered a nonlinear inductance, while line-to-line, line-to-earth capacitances, series capacitors, and grading capacitors of circuit breakers are considered linear capacitances [<xref ref-type="bibr" rid="scirp.133663-ref16">16</xref>] .</p><p>Ferroresonance oscillations depend not only on frequency but also on factors such as system voltage magnitude, initial magnetic flux condition of the transformer iron core, total core losses in the circuit, and the switching moment intervals. CCS is also susceptible to ferroresonance [<xref ref-type="bibr" rid="scirp.133663-ref17">17</xref>] .</p><sec id="s2_1"><title>2.1. Capacitor Coupled Substation (CCS)</title><p>Although the principle of operation of a CCS is derived from a CVT, CVTs are commonly utilized in transmission substations for metering and protection purposes, therefore, their load burden is low and limited [<xref ref-type="bibr" rid="scirp.133663-ref18">18</xref>] [<xref ref-type="bibr" rid="scirp.133663-ref19">19</xref>] . A simplified representation of a 400 kV/11 kV CCS selected for this study is shown on <xref ref-type="fig" rid="fig1">Figure 1</xref>. A 400 kV/11 kV CCS implies that the transmission HV is at 400 kVrms level while the tap-voltage or primary side of the distribution transformer is at 11 kVrms.</p><p>In <xref ref-type="fig" rid="fig1">Figure 1</xref>, the schematic representation of the CCS equivalent circuit is presented. Bus A represents the upstream supply side of the HV transmission network, Bus B, represents the downstream of the HV transmission network and Bus C represents the CCS tap-voltage feeding the distribution network transformer. From <xref ref-type="fig" rid="fig1">Figure 1</xref>, a Thevenin equivalent of the voltage divider (C1 and C2) is shown, with the Thevenin equivalent voltage represented as per (1) and its impedance is that of capacitors C1 and C2 as shown on (2).</p><p>V _ th = V _ in &#215; C _ 1 / ( ( C _ 1 + C _ 2 ) ) (1)</p><p>C _ th = C _ 1 + C _ 2 (2)</p><p>The formulae, (1) and (2), serve as the basis for element calculation in a CCS. The objective is to ensure that the Vout remains stable as it feeds into a downstream transformer for the distribution system. From <xref ref-type="fig" rid="fig1">Figure 1</xref>, there is also a compensating reactor (L). The reactor is used for voltage regulation. The reactor is chosen based on considerations of various factors, including feeder characteristics, transformer specifications, and the reactance and resistance of both the load and the reactor [<xref ref-type="bibr" rid="scirp.133663-ref20">20</xref>] .</p></sec><sec id="s2_2"><title>2.2. Ferroresonance Suppression Circuit (FSC)</title><p>The ferroresonance suppression circuit (FSC) is used to prevent damages due to ferroresonance in an electrical system [<xref ref-type="bibr" rid="scirp.133663-ref21">21</xref>] . A simplified representation of a CCS with FSC is shown in <xref ref-type="fig" rid="fig2">Figure 2</xref>.</p><p><xref ref-type="fig" rid="fig2">Figure 2</xref> shows the FSC connected to a CCS. The inductor (L), connected to the capacitive voltage divider is used to cancel the Thevenin impedance at 50 Hz and this is achieved by adjusting energy storage components such as they satisfy the concept represented by (3):</p><p>LC ω ∧ 2 = 1 (3)</p><p>where: ω = 2π50 for a 50 Hz system.</p><p>Satisfaction of (3) results in the output voltage being in-phase with the tap-voltage and the supply voltage. The inductor (L) is thus given by (4).</p><p>L = 1 / ( ω ∧ 2 &#215; C _ TH ) (4)</p><p>There are two main types of damping circuit operational modes; active ferroresonance suppression circuit (AFSC) and passive ferroresonance suppression circuit (PFSC).</p><sec id="s2_2_1"><title>2.2.1. FSC Active Operational Mode</title><p>In an actively operational mode, the FSC include capacitors (C), resistors (R), and iron core inductors (L) that are connected and tuned to the fundamental frequency. These elements are permanently integrated on the secondary side of a system transformer and impact the transient response of a CCS [<xref ref-type="bibr" rid="scirp.133663-ref22">22</xref>] . This parallel-connected filter is strategically implemented to address both ferroresonance and harmonic transients within the system. Operating as an open-circuit at the fundamental frequency, it transforms into a short-circuit, incorporating losses, at frequencies other than the fundamental. The inclusion of resistive losses plays a crucial role in effectively mitigating hazardous transients within the system [<xref ref-type="bibr" rid="scirp.133663-ref23">23</xref>] .</p></sec><sec id="s2_2_2"><title>2.2.2. FSC Passive Operational Mode</title><p>In a passive operational mode, the FSC consists of a power electronic control circuit in series with a resistor. This circuit activates in response to overvoltage events. Power electronic devices are employed to selectively switch a damping resistor to the secondary side of the transformer as required [<xref ref-type="bibr" rid="scirp.133663-ref24">24</xref>] .</p></sec></sec><sec id="s2_3"><title>2.3. RLC-Filter Design</title><p><xref ref-type="fig" rid="fig3">Figure 3</xref> shows the different configurations of an RLC-filter design.</p><p><xref ref-type="fig" rid="fig3">Figure 3</xref>(a) shows the schematic of a serial-parallel RLC filter, where a capacitor is connected in parallel with an iron core inductor tuned for the fundamental frequency. The resistor (R) functions as a damping resistor strategically engineered to suppress ferroresonance oscillations within a single cycle. The circuit is tuned with a high factor to effectively suppress ferroresonance oscillations at frequencies other than the fundamental frequency.</p><p>The FSC can also be represented using two distinct models. In one model (<xref ref-type="fig" rid="fig3">Figure 3</xref>(b)), the FSC is characterized with an air core inductance. Alternatively, it can be portrayed as a non-saturable transformer, as shown in <xref ref-type="fig" rid="fig3">Figure 3</xref>(c). In <xref ref-type="fig" rid="fig3">Figure 3</xref>(c) model, primary and secondary windings are connected with specified polarities. The computed value is integrated into the transformer model as a self-inductance, ensuring parallel resonance at the fundamental frequency. At frequencies other than the fundamental, only the leakage inductance comes into play, with the damping resistor responsible for reducing ferroresonance oscillations.</p></sec></sec><sec id="s3"><title>3. Methodology</title><p>A 400 kV/11 kV CCS with known parameters was developed using MATLAB/Simulink software. The model was executed and the system behaviour analysed. The main focus was on the primary and secondary sides of the distribution transformer during disturbances which were represented by switching the system ON and OFF at no-load. The system was then switched ON and OFF with a three-phase fault on the primary side of the transformer. In both operations, the interference/transient phenomenon was observed.</p><p>Subsequently, the model underwent simulation using a standard RLC filter, and once more, the behaviour of the system was observed. The simulation parameters for the CCS model used are presented on <xref ref-type="table" rid="table1">Table 1</xref>.</p><p>The parameters on <xref ref-type="table" rid="table1">Table 1</xref> were used on the MATLAB/Simulink model presented on <xref ref-type="fig" rid="fig4">Figure 4</xref>.</p><table-wrap id="table1" ><label><xref ref-type="table" rid="table1">Table 1</xref></label><caption><title> CCS Model Parameters</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Parameter</th><th align="center" valign="middle" >Description</th></tr></thead><tr><td align="center" valign="middle" >V<sub>s</sub></td><td align="center" valign="middle" >Selected Tx Line</td></tr><tr><td align="center" valign="middle" >V<sub>T</sub></td><td align="center" valign="middle" >Selected Tap Voltage</td></tr><tr><td align="center" valign="middle" >CCS Load</td><td align="center" valign="middle" >Selected load value</td></tr><tr><td align="center" valign="middle" >Downstream Load</td><td align="center" valign="middle" >Selected load value</td></tr><tr><td align="center" valign="middle" >CCS Transformer</td><td align="center" valign="middle" >Selected Transformer</td></tr><tr><td align="center" valign="middle" >C<sub>1</sub></td><td align="center" valign="middle" >Capacitor 1</td></tr><tr><td align="center" valign="middle" >C<sub>2</sub></td><td align="center" valign="middle" >Capacitor 2</td></tr><tr><td align="center" valign="middle" >L</td><td align="center" valign="middle" >Line Inductance</td></tr><tr><td align="center" valign="middle" >Tx Line Section #1</td><td align="center" valign="middle" >Selected</td></tr><tr><td align="center" valign="middle" >Tx Line Section #2</td><td align="center" valign="middle" >Selected</td></tr></tbody></table></table-wrap><p>The MATLAB/Simulink model depicted in <xref ref-type="fig" rid="fig4">Figure 4</xref> was employed to simulate the system, initially without the FSC incorporated into the circuit, and subsequently with the FSC included in the circuit. The results are presented on the figures in the following section. The interference was initially introduced by switching ON and OFF the CCS circuit breaker, and by simulating a three-phase fault within the primary side of the CCS distribution transformer. All results were observed during system switching under no-load conditions. All simulations were conducted using identical switching times. These times are presented on <xref ref-type="table" rid="table2">Table 2</xref>.</p><p>The times presented on <xref ref-type="table" rid="table2">Table 2</xref> are for the CCS breaker operations. In the simulation, all line breakers closed immediately upon initiation, while the load breaker (LB) opened simultaneously to depict a no-load system. The results and discussions are discussed below. The simulation is based on a 400kV/11kV CCS with parameters as presented on <xref ref-type="table" rid="table3">Table 3</xref> and the supply or transmission line parameters represented in <xref ref-type="fig" rid="fig5">Figure 5</xref>.</p></sec><sec id="s4"><title>4. Results and Discussions</title><p>Utilizing the model depicted in <xref ref-type="fig" rid="fig4">Figure 4</xref> from the previous section, the graphical representation of the voltage response of the primary side of the distribution transformer is presented in <xref ref-type="fig" rid="fig6">Figure 6</xref> and <xref ref-type="fig" rid="fig7">Figure 7</xref>.</p><table-wrap id="table2" ><label><xref ref-type="table" rid="table2">Table 2</xref></label><caption><title> CCS circuit breaker switching</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >CCS Circuit Breaker Position</th><th align="center" valign="middle" >Time (s)</th></tr></thead><tr><td align="center" valign="middle" >Close</td><td align="center" valign="middle" >0.2</td></tr><tr><td align="center" valign="middle" >Open</td><td align="center" valign="middle" >0.4</td></tr><tr><td align="center" valign="middle" >Close</td><td align="center" valign="middle" >0.6</td></tr><tr><td align="center" valign="middle" >Open</td><td align="center" valign="middle" >0.8</td></tr><tr><td align="center" valign="middle" >Close</td><td align="center" valign="middle" >1</td></tr></tbody></table></table-wrap><table-wrap id="table3" ><label><xref ref-type="table" rid="table3">Table 3</xref></label><caption><title> Model parameters</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Parameter</th><th align="center" valign="middle" >Value</th></tr></thead><tr><td align="center" valign="middle" >Supply</td><td align="center" valign="middle" >400 kVrms, 50 Hz</td></tr><tr><td align="center" valign="middle" >Transmission line section 1 and 2</td><td align="center" valign="middle" >300 km, 0.01273 Ω/km, 0.9337 mH/km, 0.01274 &#181;F/km</td></tr><tr><td align="center" valign="middle" >Transmission line load</td><td align="center" valign="middle" >50 MW @ 400 kV, 50 Hz</td></tr><tr><td align="center" valign="middle" >CCS C<sub>1</sub></td><td align="center" valign="middle" >0.09 πF</td></tr><tr><td align="center" valign="middle" >CCS C<sub>2</sub></td><td align="center" valign="middle" >7.5 &#181;F</td></tr><tr><td align="center" valign="middle" >L<sub>1</sub> and L<sub>2</sub></td><td align="center" valign="middle" >1 mH</td></tr><tr><td align="center" valign="middle" >Distribution Transformer</td><td align="center" valign="middle" >100 kVA, 50 Hz, 11 kV/400 V, 0.002 Rpu, 0.08 Lpu</td></tr><tr><td align="center" valign="middle" >CCS Load</td><td align="center" valign="middle" >80 kW @400 V, 50 Hz, 100 Ql, 100 Qc</td></tr><tr><td align="center" valign="middle" >FSC</td><td align="center" valign="middle" >L = 1 mH, C = 1 &#181;F, R = 1 Ω</td></tr></tbody></table></table-wrap><p>The results shown in <xref ref-type="fig" rid="fig6">Figure 6</xref> and <xref ref-type="fig" rid="fig7">Figure 7</xref> are derived from executing the model illustrated in <xref ref-type="fig" rid="fig4">Figure 4</xref> from the preceding section. <xref ref-type="fig" rid="fig6">Figure 6</xref> and <xref ref-type="fig" rid="fig7">Figure 7</xref> provide simulation results of the primary side of the CCS distribution transformer voltage response, while <xref ref-type="fig" rid="fig8">Figure 8</xref> and <xref ref-type="fig" rid="fig9">Figure 9</xref> illustrate the corresponding secondary voltage of the CCS distribution transformer.</p><p>In the South African context, this voltage is used for single-phase household supply by utilizing one line alongside the neutral or ground point, effectively converting 400 V three-phase voltage to 230 V single-phase voltage, where phase voltage (Vφ)equals toline voltage (VLL) divided by square-root-of-3.</p><p><xref ref-type="fig" rid="fig6">Figure 6</xref>, <xref ref-type="fig" rid="fig7">Figure 7</xref>, <xref ref-type="fig" rid="fig8">Figure 8</xref> and <xref ref-type="fig" rid="fig9">Figure 9</xref> present the primary and secondary voltage representations during the switching of the system under no-load conditions. It is evident that in the absence of any form of a FSC, the voltage exhibits instability and resonance. Upon each activation or deactivation of the system, a considerable amount of time is required for stabilization. Without the FSC, the voltage remains in oscillation, emphasizing the crucial role of the FSC in ensuring stability.</p><p>Upon connecting the FSC to the secondary side of the CCS distribution transformer and repeating the same switching operation, the resulting waveforms are illustrated in <xref ref-type="fig" rid="fig1">Figure 1</xref>0 and <xref ref-type="fig" rid="fig1">Figure 1</xref>1, representing the primary and secondary sides, respectively.</p><p>The identical operation, with and without the FSC, was repeated while a three-phase short-circuit fault was applied on the primary side of the CCS distribution transformer. The results are presented in <xref ref-type="fig" rid="fig1">Figure 1</xref>2, <xref ref-type="fig" rid="fig1">Figure 1</xref>3, <xref ref-type="fig" rid="fig1">Figure 1</xref>4 and <xref ref-type="fig" rid="fig1">Figure 1</xref>5 for the system with the FSC connected.</p><p>As evident from <xref ref-type="fig" rid="fig1">Figure 1</xref>0 and <xref ref-type="fig" rid="fig1">Figure 1</xref>1, the addition of a FSC stabilizes both the primary and the secondary voltages immediately after the switching operation.</p><p>When the fault is applied, the results are as shown in <xref ref-type="fig" rid="fig1">Figure 1</xref>2, <xref ref-type="fig" rid="fig1">Figure 1</xref>3, <xref ref-type="fig" rid="fig1">Figure 1</xref>4 and <xref ref-type="fig" rid="fig1">Figure 1</xref>5.</p><p>With the same switching durations, the FSC significantly contributes to rapidly stabilizing the system once the fault has been cleared during switching operations. This phenomenon is depicted in <xref ref-type="fig" rid="fig1">Figure 1</xref>6 and <xref ref-type="fig" rid="fig1">Figure 1</xref>7, showing the system’s rapid stabilization after clearing the fault condition. The incorporation of the FSC ensures a seamless transition to standard operating parameters, effectively alleviating any potential instabilities that could otherwise emerge for the transients results.</p><p>Despite <xref ref-type="fig" rid="fig1">Figure 1</xref>5 and <xref ref-type="fig" rid="fig1">Figure 1</xref>7 depicting distinct switching operations, the results achieved consistently demonstrate that the FSC effectively stabilizes any oscillations when integrated into the circuit.</p><p>Hence, it is reasonable to affirm that a conventional FSC can be incorporated in the design of a CCS. This FSC serves to mitigate voltage oscillations during both switching operations and after the clearance of a fault. The outcomes indicate that the FSC facilitates the system in sustaining the desired primary and secondary voltages at 11 kV and 400 V, respectively, following both the switching operation and fault clearance.</p></sec><sec id="s5"><title>5. Conclusions</title><p>The Capacitor Coupled Substation (CCS) offers an alternative approach to delivering electrical power directly from HV transmission lines to MV systems. This method circumvents the requirement for conventional distribution infrastructure. While the study examines distinct limitations inherent to the CCS system, a particular emphasis on voltage stability and its implications on the main transmission network were the main points of interest. The results of this study reveal two significant observations: firstly, the integration of a CCS does not exert any negative influence on the voltage of the upstream system of the transmission network; secondly, conventional technologies demonstrate proficiency in preserving the stability of the voltage on the CCS load side, notwithstanding potential disturbances such as ferroresonance resulting from switching operations, no-load switching, and system fault.</p><p>Therefore, it is reasonable to conclude that a simple RLC-based FSC can effectively ensure voltage system stability, negating the need for overly sophisticated electronic components.</p><p>As this study forms part of the proposed novel concept of Capacitor Coupled Substation with Controllable Network Transformer (CCS-CNT), the results achieved in this article add to the knowledge of voltage stability within CCS voltages under conditions of no-load switching or faults. The findings show that the conventional method of RLC filters can efficiently mitigate transients, with particular emphasis on the fact that this study used a more simplified distribution transformer.</p></sec><sec id="s6"><title>6. Recommendations</title><p>The following is the recommendation for future research:</p><p>System analysis on the ferroresonance behavior on a CCS using a non-linear distribution transformer needs to be conducted and mitigating factors studied.</p></sec><sec id="s7"><title>Acknowledgements</title><p>The author appreciates the ongoing support from Dr. BT Abe and Dr. AF Nnachi of the Tshwane University of Technology.</p></sec><sec id="s8"><title>Conflicts of Interest</title><p>The authors declare no conflicts of interest regarding the publication of this paper.</p></sec><sec id="s9"><title>Cite this paper</title><p>Nene, S.W., Abe, B.T. and Nnachi, A.F. (2024) Mitigation of Transients in Capacitor Coupled Substations Using Traditional RLC Filter Techniques. Journal of Power and Energy Engineering, 12, 60-75. https://doi.org/10.4236/jpee.2024.125003</p></sec></body><back><ref-list><title>References</title><ref id="scirp.133663-ref1"><label>1</label><mixed-citation publication-type="other" xlink:type="simple">Abdel-Hamed, A.M., El-Shafhy, M.M. and Badran, E.A. (2022) High Ohmic Reactor as a Shunt Limiter (HOR-SL) Method for Ferroresonance Elimination in the Distribution System.&lt;i&gt; &lt;/i&gt;&lt;i&gt;IEEE Access&lt;/i&gt;, 10, 134217-134229. &lt;br&gt;https://doi.org/10.1109/ACCESS.2022.3231190</mixed-citation></ref><ref id="scirp.133663-ref2"><label>2</label><mixed-citation publication-type="other" xlink:type="simple">Saulo, M.J. and Gaunt, C.T. (2015) The Impact of Capacitor Coupled Sub-Station in Rural Electrification of Sub-Saharan Africa. &lt;i&gt;International Journal of Energy and Power Engineering&lt;/i&gt;, 4, 12-29.</mixed-citation></ref><ref id="scirp.133663-ref3"><label>3</label><mixed-citation publication-type="other" xlink:type="simple">Saulo, M.J. (2014) Penetration Level of Un-Conventional Rural Electrification Technologies on Power Networks. Ph.D Thesis, University of Cape Town, Cape Town.</mixed-citation></ref><ref id="scirp.133663-ref4"><label>4</label><mixed-citation publication-type="other" xlink:type="simple">Sanaye-Pasand, M. and Aghazadeh, R. (2003) Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronics Devices. &lt;i&gt;International Conference on Power Systems Transients&lt;/i&gt;, New Orleans, 28 September-2 October 2003, 1-5. </mixed-citation></ref><ref id="scirp.133663-ref5"><label>5</label><mixed-citation publication-type="other" xlink:type="simple">Salihi, J.T. (1960) Theory of Ferroresonance. &lt;i&gt;Transactions of the American Institute of Electrical Engineers&lt;/i&gt;,&lt;i&gt; Part I&lt;/i&gt;: &lt;i&gt;Communication and Electronics&lt;/i&gt;, 87, 755-763. &lt;br&gt;https://doi.org/10.1109/TCE.1960.6368465</mixed-citation></ref><ref id="scirp.133663-ref6"><label>6</label><mixed-citation publication-type="other" xlink:type="simple">Pinheiro, P.H., Vidal, M.L., Rocha, F.F., Franca, B.W. and Fortes, M.Z. (2020) Ferroresonance Evaluation on Capacitor Voltage Transformers. &lt;i&gt;Electrical Engineering&lt;/i&gt;, 102, 1775-1783. &lt;br&gt;https://doi.org/10.1007/s00202-020-00992-x</mixed-citation></ref><ref id="scirp.133663-ref7"><label>7</label><mixed-citation publication-type="other" xlink:type="simple">Pinheiro, P.H., Vidal, M.L., Rocha, F.F. and Fortes, B.W. (2020) Ferroresonance Evaluation on Capacitor Voltage Transformers. &lt;i&gt;Electrical Engineering&lt;/i&gt;, 102, 1775-1783. &lt;br&gt;https://doi.org/10.1007/s00202-020-00992-x</mixed-citation></ref><ref id="scirp.133663-ref8"><label>8</label><mixed-citation publication-type="other" xlink:type="simple">Olanrewaju, E. and Olanrewaju, O. (2020) Rural Electrification and Profitability among Rural Women-Owned Microenterprises in Nigeria. &lt;i&gt;International Journal of Economics&lt;/i&gt;, 8, 1-11. &lt;br&gt;https://doi.org/10.34293/economics.v8i4.3381</mixed-citation></ref><ref id="scirp.133663-ref9"><label>9</label><mixed-citation publication-type="journal" xlink:type="simple"><name name-style="western"><surname>Nogay</surname><given-names> H. S. </given-names></name>,<etal>et al</etal>. (<year>2023</year>)<article-title>Forecasting of Voltage Disturbances at the Beginning of Ferroresonance Phenomena in Power Systems Using by a New Approach of Long-Short Term Memory (LSTM)</article-title><source>&lt;i&gt; &lt;/i&gt;&lt;i&gt;Journal of Engineering Research&lt;/i&gt;</source><volume> 11</volume>,<fpage> 297</fpage>-<lpage>306</lpage>.<pub-id pub-id-type="doi"></pub-id></mixed-citation></ref><ref id="scirp.133663-ref10"><label>10</label><mixed-citation publication-type="book" xlink:type="simple">Nilsson, S.L., Lima, M. and Young, D.J. (2020) AC Network Control Using Conventional Means. In: Andersen, B. and Nilsson, S., Eds., &lt;i&gt;Flexible AC Transmission Sy&lt;/i&gt;&lt;i&gt;s&lt;/i&gt;&lt;i&gt;tems&lt;/i&gt;, Springer, Cham, 51-89. &lt;br&gt;https://doi.org/10.1007/978-3-030-35386-5_3</mixed-citation></ref><ref id="scirp.133663-ref11"><label>11</label><mixed-citation publication-type="other" xlink:type="simple">Nene, S.W., Abe, B.T. and Nnachi, A.F. (2023) Modeling and Simulation of a Transmission Line Response to a 400 KV/400V Capacitor Coupled Substation. &lt;i&gt;Journal of Power and Energy Engineering&lt;/i&gt;, 11, 1-14. &lt;br&gt;https://doi.org/10.4236/jpee.2023.1112001</mixed-citation></ref><ref id="scirp.133663-ref12"><label>12</label><mixed-citation publication-type="other" xlink:type="simple">Navaei, M., Abdoos, A.A. and Shahabi, M. (2018) A New Control Unit for Electronic Ferroresonance Suppression Circuit in Capacitor Voltage Transformers. &lt;i&gt;I&lt;/i&gt;&lt;i&gt;n&lt;/i&gt;&lt;i&gt;ternational Journal of Electrical Power &amp; Energy Systems&lt;/i&gt;, 99, 281-289. &lt;br&gt;https://doi.org/10.1016/j.ijepes.2018.01.021</mixed-citation></ref><ref id="scirp.133663-ref13"><label>13</label><mixed-citation publication-type="other" xlink:type="simple">Meng, Z., Li, H., Zhang, C., Chen, M. and Chen, Q. (2019) Research on the Reliability of Capacitor Voltage Transformers Calibration Results. &lt;i&gt;Measurement&lt;/i&gt;, 146, 770-779. &lt;br&gt;https://doi.org/10.1016/j.measurement.2019.07.011</mixed-citation></ref><ref id="scirp.133663-ref14"><label>14</label><mixed-citation publication-type="other" xlink:type="simple">Martinez, E., Antonova, G. and Olguin, M. (2013) Ferroresonance Phenomenon in CFE, Its Origin and Effects. 2013 66&lt;i&gt;th Annual Conference for Protective Relay E&lt;/i&gt;&lt;i&gt;n&lt;/i&gt;&lt;i&gt;gineers&lt;/i&gt;, Texas, 8-11 April 2013, 450-466. &lt;br&gt;https://doi.org/10.1109/CPRE.2013.6822057</mixed-citation></ref><ref id="scirp.133663-ref15"><label>15</label><mixed-citation publication-type="other" xlink:type="simple">Lin, T.C., Wang, H.H. and Liu, C.H. (2021) Fault Location for Three-Ended Ring-Topology Power System Using Minimum GPS-Based Measurements and CVT/CT Sensing. &lt;i&gt;IEEE Sensors Journal&lt;/i&gt;, 21, 22019-22031. &lt;br&gt;https://doi.org/10.1109/JSEN.2021.3100772</mixed-citation></ref><ref id="scirp.133663-ref16"><label>16</label><mixed-citation publication-type="other" xlink:type="simple">Kraszewski, W., Syrek, P. and Mitoraj, M. (2022) Methods of Ferroresonance Mitigation in Voltage Transformers in 30kV Power Supply Network. &lt;i&gt;Energies&lt;/i&gt;, 15, Article 9516. &lt;br&gt;https://doi.org/10.3390/en15249516</mixed-citation></ref><ref id="scirp.133663-ref17"><label>17</label><mixed-citation publication-type="other" xlink:type="simple">Kalair, A., Abas, N., Kalair, A., Saleem, Z. and Khan, N. (2017) Review of Harmonic Analysis, Modeling and Mitigation Techniques. &lt;i&gt;Renewable and Sustainable Energy Reviews&lt;/i&gt;, 78, 1152-1187. &lt;br&gt;https://doi.org/10.1016/j.rser.2017.04.121</mixed-citation></ref><ref id="scirp.133663-ref18"><label>18</label><mixed-citation publication-type="other" xlink:type="simple">Hepziba, R.J., Balaji, G., Muralikrishma, R. and Rathinavel, S. (2024) A Case Study on Transformer Ferroresonance for Subsea Cable Connected 230kV Substations Using PSCAD. &lt;i&gt;Electric Power Systems Research&lt;/i&gt;, 230, Article ID: 110192. &lt;br&gt;https://doi.org/10.1016/j.epsr.2024.110192</mixed-citation></ref><ref id="scirp.133663-ref19"><label>19</label><mixed-citation publication-type="other" xlink:type="simple">Fathi, S.H. and Abbasi, A. (2018) New Technique for Elimination of Ferroresonant Oscillations in Series Capacitor of Power System. &lt;i&gt;Asian Journal of Scientific R&lt;/i&gt;&lt;i&gt;e&lt;/i&gt;&lt;i&gt;search&lt;/i&gt;, 11, 203-221. &lt;br&gt;https://doi.org/10.3923/ajsr.2018.203.221</mixed-citation></ref><ref id="scirp.133663-ref20"><label>20</label><mixed-citation publication-type="other" xlink:type="simple">EL-Shafhy, M.M., Abdel-Hamed, A.M. and Badran, E.A. (2022) Ferroresonance in Distribution Systems&amp;#8212;State of the Art. &lt;i&gt;Przeglad&lt;/i&gt;&lt;i&gt; &lt;/i&gt;&lt;i&gt;Elektrotechniczny&lt;/i&gt;, 98, 1. &lt;br&gt;https://doi.org/10.15199/48.2022.11.01</mixed-citation></ref><ref id="scirp.133663-ref21"><label>21</label><mixed-citation publication-type="other" xlink:type="simple">Aminifar, F., Abedini, M., Amraee, T., Jafarian, P., Samimi, M.H. and Shahidehpour, M. (2022) A Review of Power System Protection and Asset Management with Machine Learning Techniques. &lt;i&gt;Energy Systems&lt;/i&gt;, 13, 855-892. &lt;br&gt;https://doi.org/10.1007/s12667-021-00448-6</mixed-citation></ref><ref id="scirp.133663-ref22"><label>22</label><mixed-citation publication-type="other" xlink:type="simple">Alghaythi, M.L., Irudayaraj, G.C., Ramu, S.K., Govindaraj, P. and Vairavasundaram, I. (2023) Mathematical Modeling and Analysis of Capacitor Voltage Balancing for Power Converters with Fewer Switches. &lt;i&gt;Sustainability&lt;/i&gt;, 15, Article 10698. &lt;br&gt;https://doi.org/10.3390/su151310698</mixed-citation></ref><ref id="scirp.133663-ref23"><label>23</label><mixed-citation publication-type="other" xlink:type="simple">Akpan, U., Essien, M. and Isihak, S. (2013) The Impact of Rural Electrification on Rural Micro-Enterprises in Niger Delta, Nigeria. &lt;i&gt;Energy for Sustainable Development&lt;/i&gt;, 17, 504-509. &lt;br&gt;https://doi.org/10.1016/j.esd.2013.06.004</mixed-citation></ref><ref id="scirp.133663-ref24"><label>24</label><mixed-citation publication-type="other" xlink:type="simple">Abdel-Hamed, A.M., El-Shafhy, M.M. and Badran, E.A. (2023) Investigating Ferroresonance in the Distribution Zone. 2022 23&lt;i&gt;rd International Middle East Power Systems Conference&lt;/i&gt; (&lt;i&gt;MEPCON&lt;/i&gt;), Cairo, 13-15 December 2022, 1-8. &lt;br&gt;https://doi.org/10.1109/MEPCON55441.2022.10021717</mixed-citation></ref></ref-list></back></article>