<?xml version="1.0" encoding="UTF-8"?><!DOCTYPE article  PUBLIC "-//NLM//DTD Journal Publishing DTD v3.0 20080202//EN" "http://dtd.nlm.nih.gov/publishing/3.0/journalpublishing3.dtd"><article xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink" dtd-version="3.0" xml:lang="en" article-type="research article"><front><journal-meta><journal-id journal-id-type="publisher-id">WJET</journal-id><journal-title-group><journal-title>World Journal of Engineering and Technology</journal-title></journal-title-group><issn pub-type="epub">2331-4222</issn><publisher><publisher-name>Scientific Research Publishing</publisher-name></publisher></journal-meta><article-meta><article-id pub-id-type="doi">10.4236/wjet.2023.111003</article-id><article-id pub-id-type="publisher-id">WJET-122519</article-id><article-categories><subj-group subj-group-type="heading"><subject>Articles</subject></subj-group><subj-group subj-group-type="Discipline-v2"><subject>Chemistry&amp;Materials Science</subject><subject> Engineering</subject></subj-group></article-categories><title-group><article-title>
 
 
  Contribution to Asymmetrical Compensation through Parallel Controllers of FACTS (STATCOM)—IPC 240 Dual for a Power Transmission Line
 
</article-title></title-group><contrib-group><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Kengne</surname><given-names>Chatue Charlène Steva</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Mengata</surname><given-names>Mengounou Ghislain</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Koko</surname><given-names>Koko Joseph</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref><xref ref-type="corresp" rid="cor1"><sup>*</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Batassou</surname><given-names>Guilzia Jeannot</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Nneme</surname><given-names>Nneme Leandre</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref></contrib></contrib-group><aff id="aff1"><addr-line>Laboratory of Computer and Automatic Engineering, UFD of Engineering Sciences, ENSET, University of Douala, Douala, 
Cameroon</addr-line></aff><pub-date pub-type="epub"><day>29</day><month>12</month><year>2022</year></pub-date><volume>11</volume><issue>01</issue><fpage>20</fpage><lpage>40</lpage><history><date date-type="received"><day>22,</day>	<month>July</month>	<year>2022</year></date><date date-type="rev-recd"><day>15,</day>	<month>January</month>	<year>2023</year>	</date><date date-type="accepted"><day>18,</day>	<month>January</month>	<year>2023</year></date></history><permissions><copyright-statement>&#169; Copyright  2014 by authors and Scientific Research Publishing Inc. </copyright-statement><copyright-year>2014</copyright-year><license><license-p>This work is licensed under the Creative Commons Attribution International License (CC BY). http://creativecommons.org/licenses/by/4.0/</license-p></license></permissions><abstract><p>
 
 
  This work is part of the resolution of problems encountered on a 225
   
  KV MANGOMBE-OYOMABANG line. This line is characterized by important technical losses, so that the voltage injected in the busbar is always lower than 200
  
  kV. The main objective of this work is to show the new solutions that can provide a combined FACTS-STATCOM and IPC 240 dual system on this line. Then to show the limitation of STATCOM compared to RPI 240. The results obtained allowed us to observe that in symmetrical operation the STATCOM improves the voltage profile on the busbar and in asymmetrical operation we found that it continues to regulate the voltage of each phase despite the unbalance. But the system remains too unbalanced because of the sequence current flow. The IPC 240 corrects this limitation, allowing asymmetrical operation of the line in an emergency while providing continuous service to the load.
 
</p></abstract><kwd-group><kwd>FACTS</kwd><kwd> STATCOM</kwd><kwd> IPC 240 Dual</kwd><kwd> Symmetry</kwd><kwd> Asymmetry</kwd><kwd> Contingency</kwd><kwd> Voltage Profile</kwd></kwd-group></article-meta></front><body><sec id="s1"><title>1. Introduction</title><p>For several years, electrical energy producers have been striving to guarantee the quality of electrical energy, the first efforts have focused on continuity of service and then on compensation technology by FACTS (Flexible Alternative Current Transmission System) in order to always make access to energy available to the user. They are electronic or static systems that allow the adjustment of one or more parameters of the network, they are used to control the distribution of loads in the network, thus improving the transit capacity and reducing losses, to control the voltage in one point or ensure the dynamic stability of the electricity transmission networks and the production groups connected to them. Current Flexible Alternating Current Transmission Systems (FACTS) cannot handle the widespread problem of high short circuit levels on power transmission lines [<xref ref-type="bibr" rid="scirp.122519-ref1">1</xref>] . The traditional solution, which consists of splitting the networks, undermines their operating flexibility and even their reliability. The Interphase Power Regulator (IPR) is an innovative solution for environments with high short-circuit levels; they are part of the current of thought of the concept of FACTS networks. It will be a question for us of modeling and simulating via the simulation software MATLAB Simulink the STATCOM and the IPC 240 dual with three branches, in order to show the limit of the STATCOM compared to the IPC 240.</p></sec><sec id="s2"><title>2. Materials and Methods</title><sec id="s2_1"><title>2.1. Materials</title><p>FACTS are auxiliary power electronic equipment used to control load distribution in the network, thus improving the transit capacity and reducing losses, to control the voltage at a point or ensure the dynamic stability of electricity transmission networks and production groups connected to them. The development of IPC technology was mainly motivated by the need to create new power flow controllers to overcome network operating limitations caused by too high short-circuit levels [<xref ref-type="bibr" rid="scirp.122519-ref2">2</xref>] .</p><p>As materials we used; the Matlab Simulink software as simulation software which allowed us to test our model and a PC as a working tool (<xref ref-type="table" rid="table1">Table 1</xref>).</p></sec><sec id="s2_2"><title>2.2. Methods</title><sec id="s2_2_1"><title>2.2.1. Statcom Modeling</title><p>For the simplified modeling of the STATCOM it is assumed that the DC circuit consists of a constant voltage source. In this model the equivalent circuit will be represented as follows (<xref ref-type="fig" rid="fig1"><xref ref-type="fig" rid="fig">Figure </xref>1</xref>).</p><p>Considering that:</p><p>V &#175; s h ( d , q ) = V s h d + j V s h q = v cos θ + j v sin θ (1)</p><p>V: being the modulus of the injected voltage which depends directly on the DC voltage U<sub>dc</sub> and can be expressed by [<xref ref-type="bibr" rid="scirp.122519-ref4">4</xref>] :</p><p>V = m ∗ U d c (2)</p><table-wrap id="table1" ><label><xref ref-type="table" rid="table1">Table 1</xref></label><caption><title> Characteristics of the MANGOMBE-OYOMABANG transmission line [<xref ref-type="bibr" rid="scirp.122519-ref3">3</xref>] </title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Line</th><th align="center" valign="middle" >Type</th><th align="center" valign="middle" >Level [kV]</th><th align="center" valign="middle" >Length [km]</th><th align="center" valign="middle" >R1 (ohm)</th><th align="center" valign="middle" >X1 [Ω]</th><th align="center" valign="middle" >B1 [μS]</th><th align="center" valign="middle" >R0 [Ω]</th><th align="center" valign="middle" >X0 [Ω]</th><th align="center" valign="middle" >B0 [μS]</th><th align="center" valign="middle" >IMAX [A]</th></tr></thead><tr><td align="center" valign="middle" >Man-Oyo</td><td align="center" valign="middle" >ALMELEC 225,366 mm<sup>2</sup></td><td align="center" valign="middle" >225</td><td align="center" valign="middle" >168</td><td align="center" valign="middle" >14.77</td><td align="center" valign="middle" >69.72</td><td align="center" valign="middle" >460.15</td><td align="center" valign="middle" >15.72</td><td align="center" valign="middle" >140.62</td><td align="center" valign="middle" >249.48</td><td align="center" valign="middle" >600</td></tr></tbody></table></table-wrap><p>m: is the modulation index it only depends on the type of inverter. Substituting Equations (2) and (1) we get:</p><p>V d − m U d c cos θ = R s h ⋅ I s h d + L s h ⋅ d I s h d d t − L s h ⋅ I s h q V d − m V d c sin θ = R s h ⋅ I s h q + L s h ⋅ d I s h q d t − L s h ⋅ I s h d (3)</p><p>The power flowing between the capacitor and the voltage inverter can be described by Equation (4) and at the same time verify the following equality:</p><p>P s h = 3 2 ( V s h d ⋅ I s h d + V s h q ⋅ I s h q ) U d c I d c = 3 2 ( V s h d ⋅ I s h d + V s h q ⋅ I s h q ) (4)</p><p>The current I<sub>dc</sub> is defined as being the sum of the capacitive current “ic” and the resistive current “irc” in the branch of the resistor R<sub>dc</sub>.</p><p>I d c = C d U d c d t + U d c R c (5)</p><p>From these equations we can derive the dynamic equation of the continuous side of the following STATCOM:</p><p>C d U d c d t = 3 2 m ( I s h d cos θ + I s h q sin θ ) − U d c R c (6)</p><p>Previous equations form the state equation system of STATCOM taking into account the variations of the voltage of the DC circuit which is written in the following matrix form.</p><p>d d t [ I s h d I s h q U d c ] = [ − R L s h 0 − m L s h cos θ − ω − R L s h − m L s h sin θ 3 2 m c cos θ − 3 2 m c sin θ 1 R e C ] [ I s h d I s h q U d c ] + [ 1 L s h 0 0 1 L s h 0 0 ] [ V d V q ] (7)</p><p>It can be observed that there are two control parameters in this system with three state parameters to be controlled and only two quantities can be controlled independently. This system that must be linearized around an operating point will be of the following form:</p><p>d d t [ I s h d I s h q U d c ] = [ − R L s h 0 − m L s h cos θ 0 − ω − R L s h − m L s h sin θ 0 3 2 m c cos θ 0 − 3 2 m c sin θ 0 1 R e C ] [ I s h d I s h q U d c ]   + [ 1 L s h 0 m L s h U d c 0 sin θ 0 0 1 L s h m L s h U d c 0 cos θ 0 0 0 − 3 2 m c ( I s h d sin θ 0 + I s h q cos θ 0 ) ] [ V d V q θ ] (8)</p><p>The reactive current is controlled independently to control the reactive power flow and the other parameters are used to keep the DC voltage U<sub>dc</sub> constant.</p></sec><sec id="s2_2_2"><title>2.2.2. Determination of References</title><p>Considering the simplified model represented by the system of Equation (8) above [<xref ref-type="bibr" rid="scirp.122519-ref5">5</xref>] :</p><p>d d t [ I s h d I s h q ] = [ − R s h L s h w − w − R s h L s h ] ⋅ [ I s h d I s h q ] + 1 L s h ⋅ [ V d − V s h d V q − V s h q ] (9)</p><p>On the control vector, the following change of variable is made:</p><p>1 L s h ⋅ [ V d − V s h d V q − V s h q ] = [ X 1 X 2 ] 5 (10)</p><p>With;</p><p>X 2 = 1 L s h ( V d − V s h q ) (11)</p><p>and;</p><p>X 1 = 1 L s h ( V q − V s h q ) (12)</p><p>Are the new command quantities. From the first equation of the system (10) we will have:</p><p>d I s h d d t = − R s h L s h I s h d + w ⋅ I s h q + X 1 (13)</p><p>By applying the Laplace transformation to this equation, we obtain:</p><p>( S + R s h L s h ) I s h d = w ⋅ I s h q + X 1 (14)</p><p>From where we arrive at the transfer according to the following:</p><p>I s h q X ˜ 1 = 1 S + R s h L s h (15)</p><p>Our order in reality is in X 1 and like X ˜ 1 = ω ⋅ I s h q + X 1 , we must therefore add the term ω ⋅ I s h q to find X ˜ 1 at the input of this transfer as shown in the diagram in the following <xref ref-type="fig" rid="fig2"><xref ref-type="fig" rid="fig">Figure </xref>2</xref>.</p><p>In the same way, taking the second equation of the previous model, we find the transfer I s h q in terms of X ˜ 2 following:</p><p>I s h q X ˜ 2 = 1 S + R s h L s h (16)</p><p>With,</p><p>X ˜ 2 = ω I s h d + X 2 (17)</p><p>The following diagram summarizes this transfer (<xref ref-type="fig" rid="fig3"><xref ref-type="fig" rid="fig">Figure </xref>3</xref>).</p><p>From what we have just seen we see that there is a natural coupling in the transfers of Currents I<sub>shd</sub> and I<sub>shq</sub>.</p><p>To eliminate this coupling, we use the compensation method and with PI regulators, we can control the output currents of the STATCOM and make them follow their instructions I<sub>shd</sub> and I<sub>shq</sub> as shown in the block diagram of <xref ref-type="fig" rid="fig4"><xref ref-type="fig" rid="fig">Figure </xref>4</xref>.</p><p>In the same way for the reactive current we must add the component ω ⋅ I s h d and finally arrived at the STATCOM regulation scheme by the decoupled Watt-Var method of <xref ref-type="fig" rid="fig5"><xref ref-type="fig" rid="fig">Figure </xref>5</xref>.</p></sec><sec id="s2_2_3"><title>2.2.3. Modeling of the Rpi 240 for Asymmetric Compensation of Transmission Lines</title><p>The topology of a transmission line equipped with dual RPIs is shown in <xref ref-type="fig" rid="fig6"><xref ref-type="fig" rid="fig">Figure </xref>6</xref>.</p><p>&#183; N1 and N2: connection nodes to the energy source and to the load.</p><p>&#183; RPI-S, RPI-R: RPI connected to source and load respectively.</p><p>&#183; ACL: Logic control automaton for the synchronization of the two RPIs.</p><p>&#183; D1 to D6: Intelligent circuit breaker with single-phase tripping.</p><p>&#183; Is_X: RPI-S input current intensity for phases X ϵ [<xref ref-type="bibr" rid="scirp.122519-ref1">1</xref>] .</p><p>&#183; Ir_X: Current intensity towards the load for phases X ϵ [<xref ref-type="bibr" rid="scirp.122519-ref1">1</xref>] .</p></sec><sec id="s2_2_4"><title>2.2.4. Dimensions of the Elements of the RPI 240 Has Three Branches</title><p>We will use the Fortescue transformation in order to simplify the analysis of the unbalanced three-phase electrical system. This is mathematically a basic change. The basic idea is that an asymmetric system of N phrasers (3 for three-phase) can be decomposed as the sum of N symmetric systems. The Fortescue transformation is thus also called the method of symmetric components. A three-phase system, whether currents, voltages, fluxes, etc., is thus broken down into three balanced (or symmetrical) systems: Direct, Inverse, Homopolar [<xref ref-type="bibr" rid="scirp.122519-ref8">8</xref>] . Let’s pose</p><p>F = [ 1 1 1 a 2 a 1 a a 2 1 ] (18)</p><p>Fortescue’s Matrix</p><p>Vs _abc = ( Vs _A Vs _B Vs _C ) ;       Vr _abc = ( Vr _A Vr _B Vr _C ) (19)</p><p>The simple voltage vectors at the source (s) and at the load (r) of a power transmission line.</p><p>Vs _ 120 = ( Vs _A 1 Vs _A 2 Vs _A 0 ) ;       Vr _ 120 = ( Vr _A 1 Vr _A 2 Vr _A 0 ) (20)</p><p>The source and load voltage vectors of the forward (1) and reverse (2) systems of a transmission line. The same for the current intensities</p><p>Is _abc = ( Is _A Is _B Is _C ) ;       Ir _abc = ( Ir _A Ir _B Ir _C ) (21)</p><p>The source and load line current intensities vectors on a transmission line.</p><p>Is _ 120 = ( Is _A 1 Is _A 2 Is _A 0 ) ;       Ir _ 120 = ( Ir _A 1 Ir _A 2 Ir _A 0 ) (22)</p><p>The symmetrical components of source and load currents of a transmission line [<xref ref-type="bibr" rid="scirp.122519-ref9">9</xref>] .</p><p>For the tensions</p><p>Vs _ 120 = F − 1 Vs _abc Vr _ 120 = F − 1 Vr _abc (23)</p><p>For the intensities</p><p>Is _ 120 = F − 1 Is _abc Ir _ 120 = F − 1 Ir _abc (24)</p><p>a = e j 2 π / 3 : Positive rotation vector operator 1, 2, 0: direct, reverse and homopolar system respectively</p></sec><sec id="s2_2_5"><title>2.2.5. Sizing of the Reactances of the Inverse System Compensator</title><p>This dimensioning can be done in three steps:</p><p>Step 1: Calculation of the phase-to-neutral voltage across the terminals of the compensator elements: [<xref ref-type="bibr" rid="scirp.122519-ref10">10</xref>]</p><p>U _ A B = V _ A − V _ B U _ B C = V _ B − V _ C = a 2 U _ A B U _ C A = V _ C − V _ A = a U _ A B (25)</p><p>By combining this system of equations with that which describes the simple tensions in their symmetrical components, one obtains:</p><p>V _ A 1 = V _ A B ∠ − 30 ˚ 3 = V _ A N V _ A 2 = 0 (26)</p><p>The voltage of the direct system V<sub>A</sub><sub>1</sub> at the terminals of the elements of the compensator is equal to the phase-to-neutral voltage at the source V<sub>AN</sub>, however, V<sub>An</sub><sub>0</sub> remains undetermined [<xref ref-type="bibr" rid="scirp.122519-ref11">11</xref>] .</p><p>Step 2: Computing the intensity of the compensator current.</p><p>I _ A = I _ A 1 + I _ A 2 = − I _ 2 I _ B = a 2 I _ A 1 + a I _ A 2 = − a I _ 2 I _ c = a I _ A 1 + a 2 I _ A 2 = − a 2 I _ 2 (27)</p><p>I<sub>A</sub><sub>1</sub> = 0; I<sub>A</sub><sub>2</sub> = −I<sub>2</sub></p><p>Step 3: Computing the reactances of the compensator We can rewrite equation:</p><p>V _ A 1 = I _ A 1 Z _ a 0 + I _ A 2 Z _ a 2 V _ A 2 = I _ A 1 Z _ a 1 + I _ A 2 Z _ a 0 V _ A 0 = I _ A 1 Z _ a 2 + I _ A 2 Z _ a 1 (28)</p><p>V _ A 1 = − I _ 2 Z _ a 2 = V _ A N V _ A 2 = − I _ 2 Z _ a 0 = 0 V _ A 0 = − I _ 2 Z _ a 1 = ? (29)</p><p>From were</p><p>Z _ a 2 = V _ A N − I _ 2 = R 2 + j X 2 (30)</p><p>R<sub>2</sub> and X<sub>2</sub> are respectively resistance and reactance of the inverse system.</p><p>R 2 + j X 2 = 3 V A S − I _ A S = 225000 3 ∠ 12 ˚ 3.624 &#215; 10 2 + j 1.1751 &#215; 10 2 = 703.8497 − j 139.1417 (31)</p><p>The conclusions of the equations make it possible to write [<xref ref-type="bibr" rid="scirp.122519-ref11">11</xref>] :</p><p>Z _ a = 0 + j X a = Z _ a 1 + ( R 2 + j X 2 ) Z _ b = 0 + j X b = a 2 Z _ a 1 + a ( R 2 + j X 2 ) Z _ c = 0 + j X c = a Z _ a 1 + a 2 ( R 2 + j X 2 ) (32)</p><p>As a = − 0.5 + j 3 2 ; a 2 = − 0.5 − j 3 2 and taking into account the previous equations we obtain:</p><p>Z _ a 1 = − R 2 + j X 2 (33)</p><p>From were</p><p>Z _ a = 0 + j X a = − R 2 + j X 2 + ( R 2 + j X 2 ) ⇒ X a = 2 X 2 = − 278.2834   Ω (34)</p><p>Z _ b = 0 + j X b = ( − 0.5 − j 3 2 ) ( − R 2 + j X 2 ) + ( − 0.5 + j 3 2 ) ( R 2 + j X 2 ) ⇒ X b = 3 R 2 − X 2 = 1358.245141   Ω (35)</p><p>Z _ c = 0 + j X c = ( − 0.5 + j 3 2 ) ( − R 2 + j X 2 ) + ( − 0.5 − j 3 2 ) ( R 2 + j X 2 ) ⇒ X c = − 3 R 2 − X 2 = − 1079.91174   Ω (36)</p><p>The same developments can be carried out if the fault occurs on phases B and C. Finally, the expressions for the compensation reactances of the reverse system are given in <xref ref-type="table" rid="table2">Table 2</xref> according to the contingency phase.</p></sec></sec></sec><sec id="s3"><title>3. Results and Discussion</title><p>In this part, we will simulate the STATCOM and RPI 240 dual three-legged devices that were modeled in the previous chapter. These simulations will allow us to show the contribution of the STATCOM and RPI 240 dual three-branch devices in solving the problems encountered by the transmission network managers on the 225 kV MANGOMBE-OYOMABANG line. Thereafter we will present the results of the simulations obtained on MATLAB/Simulink, and finally we will make an interpretation of these results.</p><sec id="s3_1"><title>3.1. Network Simulation without Compensator</title><p><xref ref-type="fig" rid="fig7"><xref ref-type="fig" rid="fig">Figure </xref>7</xref> below shows the 225 kV MANGOMBE-OYOMABANG line with a load at MANGOMBE, and another at OYOMABANG. We are interested in the voltage and powers at MANGOMBE and OYOMABANG busbars.</p><table-wrap id="table2" ><label><xref ref-type="table" rid="table2">Table 2</xref></label><caption><title> Expression of compensator reactances</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Reference phase (faulty)</th><th align="center" valign="middle" >Expression</th><th align="center" valign="middle" >Value of retances</th></tr></thead><tr><td align="center" valign="middle" >A</td><td align="center" valign="middle" >X a = X a a = 2 X 2 X b = X b a = 3 R 2 − X 2 X c = X c a = − 3 R 2 − X 2</td><td align="center" valign="middle" >X<sub>aa</sub> = 278.2834 Ω X<sub>ba</sub> = 1358.245141 Ω X<sub>ca</sub> = 1079.91174 Ω</td></tr><tr><td align="center" valign="middle" >B</td><td align="center" valign="middle" >X a = X a b = − 3 R 2 − X 2 X b = X b b = 2 X 2 X c = X c b = 3 R 2 − X 2</td><td align="center" valign="middle" >X<sub>ab</sub> = 1079.91174 Ω X<sub>bb</sub> = 278.2834 Ω X<sub>cb</sub> = 1358.245141 Ω</td></tr><tr><td align="center" valign="middle" >C</td><td align="center" valign="middle" >X a = X a c = 3 R 2 − X 2 X b = X b c = − 3 R 2 − X 2 X c = X c c = 2 X 2</td><td align="center" valign="middle" >X<sub>ac</sub> = 1358.245141 Ω X<sub>bc</sub> = 1079.91174 Ω X<sub>cc</sub> = 278.2834 Ω</td></tr></tbody></table></table-wrap></sec><sec id="s3_2"><title>3.2. Types of Voltage in Mangombe and Oyomabang (<xref ref-type="fig" rid="fig8"><xref ref-type="fig" rid="fig">Figure </xref>8</xref>)</title><p>The first graph displays the three-phase signal of the voltage at MANGOMBE, and the second the voltage at OYOMABANG.</p><p>In the presence of the load, the voltage amplitude at OYOMABANG is 1.571 &#215; 10<sup>5</sup> or 157.1 kV or at MANGOMBE is 1.833 &#215; 10<sup>5</sup> or 182.9 kV. Thus, a voltage drop is observed which is justified by the inrush of the current of the load which traverses the line (<xref ref-type="table" rid="table3">Table 3</xref>).</p><table-wrap id="table3" ><label><xref ref-type="table" rid="table3">Table 3</xref></label><caption><title> Indication of wattmeters</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >BUS</th><th align="center" valign="middle" >Voltage</th><th align="center" valign="middle" >Active power P</th><th align="center" valign="middle" >Reactive power Q</th></tr></thead><tr><td align="center" valign="middle" >MANGOMBE</td><td align="center" valign="middle" >182.9 kV</td><td align="center" valign="middle" >1.91 &#215; 10<sup>8</sup></td><td align="center" valign="middle" >1.439 &#215; 10<sup>8</sup></td></tr><tr><td align="center" valign="middle" >OYOMABANG</td><td align="center" valign="middle" >157.1 kV</td><td align="center" valign="middle" >8.772 &#215; 10<sup>7</sup></td><td align="center" valign="middle" >5.118 &#215; 10<sup>7</sup></td></tr></tbody></table></table-wrap></sec><sec id="s3_3"><title>3.3. Model of the Line with the Statcom (<xref ref-type="fig" rid="fig9"><xref ref-type="fig" rid="fig">Figure </xref>9</xref>)</title><p>When the STATCOM is not in operation, the “natural” power flow on the transmission line is 223 MW from bus B1 to B2. This STATCOM is a phasor model of a typical three level PWM STATCOM. The simulation of this model gave the following results.</p></sec><sec id="s3_4"><title>3.4. Voltage and Current Curves after Insertion of the Statcom in Mangombe and Oyomabang</title><p><xref ref-type="fig" rid="fig1"><xref ref-type="fig" rid="fig">Figure </xref>1</xref>0 displays the voltage signal at OYOMABANG before and after insertion of the STATCOM. At the OYOMABANG busbar level, we see a</p><p>marked improvement in the voltage profile, which goes from 157.1 kV to 178.9 kV. However, before the insertion of the STATCOM, the voltage drop was 25.8 kV. This means that the 25.8 kV drop has been reduced to 4.4 kV by the STATCOM and at the same time the power flow has increased and the loads sufficiently supplied (<xref ref-type="fig" rid="fig1"><xref ref-type="fig" rid="fig">Figure </xref>1</xref>1 &amp; <xref ref-type="table" rid="table4">Table 4</xref>).</p><table-wrap id="table4" ><label><xref ref-type="table" rid="table4">Table 4</xref></label><caption><title> Indication of the wattmeters after insertion of the STATCOM</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >BUS</th><th align="center" valign="middle" >Voltage</th><th align="center" valign="middle" >Active power P</th><th align="center" valign="middle" >R&#233;active power Q</th></tr></thead><tr><td align="center" valign="middle" >MANGOMBE</td><td align="center" valign="middle" >183.3 kV</td><td align="center" valign="middle" >2.18 &#215; 10<sup>8</sup></td><td align="center" valign="middle" >7.492 &#215; 10<sup>7</sup></td></tr><tr><td align="center" valign="middle" >OYOMABANG</td><td align="center" valign="middle" >178.9 kV</td><td align="center" valign="middle" >1.138 &#215; 10<sup>8</sup></td><td align="center" valign="middle" >6.64 &#215; 10<sup>7</sup></td></tr></tbody></table></table-wrap></sec><sec id="s3_5"><title>3.5. Model of the Line with the Statcom in Asymmetrical Operation (<xref ref-type="fig" rid="fig1"><xref ref-type="fig" rid="fig">Figure </xref>1</xref>2)</title></sec><sec id="s3_6"><title>3.6. Voltage Trends before and after Insertion of the STATCOM in MANGOMBE</title><p><xref ref-type="fig" rid="fig1"><xref ref-type="fig" rid="fig">Figure </xref>1</xref>3 displays the voltage signal at MANGOMBE before and after insertion of the STATCOM, in asymmetrical operation (single-phase short-circuit), there is an imbalance in the voltage at MANGOMBE. The first graph shows the voltage at MANGOMBE, of the faulty phase Va = 183.3 kV, and of the two other healthy phases Vb = Vc = 182.9 kV, before insertion of the STATCOM. The second graph displays the voltage Va = 183.2 Kv of the faulty phase, and of the two other healthy phases Vb = Vc = 183.3 kV, after insertion of the STATCOM. It can be seen that the STATCOM plays its role of voltage regulation despite the voltage imbalance at MANGOMBE (<xref ref-type="table" rid="table5">Table 5</xref>).</p><table-wrap id="table5" ><label><xref ref-type="table" rid="table5">Table 5</xref></label><caption><title> Summary of results</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Premises</th><th align="center" valign="middle" >Voltages without Statcom insertion (kV)</th><th align="center" valign="middle" >Voltages with insertion Statcom (kV)</th><th align="center" valign="middle" >Voltages with insertion Statcom, in asymmetric operation (kv)</th><th align="center" valign="middle" >Active power without Statcom (MW)</th><th align="center" valign="middle" >Active power with Statcom (MW)</th><th align="center" valign="middle" >Active power with Statcom, in operation Asym&#233;trique (MW)</th><th align="center" valign="middle" >Reactive power without Statcom (MW) (MVar)</th><th align="center" valign="middle" >Active power with Statcom (MW) (MVar)</th><th align="center" valign="middle" >Reactive power without Statcom (MVar) in asymmetric operation</th></tr></thead><tr><td align="center" valign="middle" >MANGOMBE</td><td align="center" valign="middle" >182.9</td><td align="center" valign="middle" >183.3</td><td align="center" valign="middle" >Va = 183.3 Vb = 183.2 Vc = 183.2</td><td align="center" valign="middle" >191</td><td align="center" valign="middle" >218</td><td align="center" valign="middle" >100.4</td><td align="center" valign="middle" >143.9</td><td align="center" valign="middle" >749.2</td><td align="center" valign="middle" >8.119</td></tr><tr><td align="center" valign="middle" >OYOMABANG</td><td align="center" valign="middle" >157.1</td><td align="center" valign="middle" >178.9</td><td align="center" valign="middle" >Va = 132.2 Vb = 177.3 Vc = 177.3</td><td align="center" valign="middle" >87.72</td><td align="center" valign="middle" >113.8</td><td align="center" valign="middle" >95.24</td><td align="center" valign="middle" >51.18</td><td align="center" valign="middle" >66.4</td><td align="center" valign="middle" >55.55</td></tr></tbody></table></table-wrap><p>Before insertion of the STATCOM, the rms voltages measured between phase-phase at the busbars were lower than the default admissible value (&#177;10). After inserting the STATCOM, we see a marked improvement in the voltage profile.</p><p>The table above presents a summary of the results obtained before and after the insertion of the STATCOM. It can be seen that the STATCOM provides good voltage regulation by generating or absorbing reactive power on the bus to which it is connected, thus improving the voltage profile at OYOMABANG.</p><p>The statcom generates a voltage in phase with the network, which is why the voltage of phase A, Va is increased from 0 kV to 132.2 kV. Also generating reactive power to improve the voltage profile at OYOMABANG. This counterpart of the line remains unbalanced and the imbalance is passed on to the loads.</p></sec><sec id="s3_7"><title>3.7. Model of the Line Equipped with Two Dual IPCs</title><p><xref ref-type="fig" rid="fig1"><xref ref-type="fig" rid="fig">Figure </xref>1</xref>4 below presents the simulation of our transmission line equipped with two RPI 240 with three branches, for the Asymmetrical compensation of the line. Each branch is equipped with three reactances for the compensation of the direct and reverse sequence, the compensation of the homopolar sequence cannot be done in the same block, if it consists in directing the homopolar currents towards the earth, it will be done with the Yd transformers at source and load (TH1 and TH2) as we saw in chapter two. The simulation of this line</p><p>gave the following results.</p><p>Voltage curves at the input and at the output of each IPC.</p></sec><sec id="s3_8"><title>3.8. Shapes of the Voltage at the Input and at the Output of Each IPC (<xref ref-type="fig" rid="fig1"><xref ref-type="fig" rid="fig">Figure </xref>1</xref>5)</title></sec><sec id="s3_9"><title>3.9. Current Samples (<xref ref-type="fig" rid="fig1"><xref ref-type="fig" rid="fig">Figure </xref>1</xref>6)</title><p>In the absence of an incident, the phase voltage angle in the sub-network:</p><p>&#183; 1<sup>st</sup> RPI entry: 11.66˚ → 1<sup>st</sup> RPI exit: 97.84˚.</p><p>&#183; 2<sup>nd</sup> RPI input: 90.48˚→load: 0.32˚.</p><p>The angle difference between the output of the 1<sup>st</sup> RPI and the input of the 2<sup>nd</sup> RPI is due to the inductance of the line while that between the input of the 1<sup>st</sup> RPI and the load represents the load angle thus restored.</p><p>In the figure, it is clear that the second RPI allows to restore the angle of the source current intensity.</p></sec><sec id="s3_10"><title>3.10. Simulations of the Contingency Line (Phase A)</title><p><xref ref-type="fig" rid="fig1"><xref ref-type="fig" rid="fig">Figure </xref>1</xref>7 presents the simulation of the line in contingency as well as the reconfiguration of the IPCs after a single-phase short circuit.</p><sec id="s3_10_1"><title>3.10.1. Voltage Samples</title><p>During the contingency, the voltages on the side of the energy source and the load are sinusoidal</p><p><xref ref-type="fig" rid="fig1"><xref ref-type="fig" rid="fig">Figure </xref>1</xref>8(a) displays the three-phase signal of the voltage at the level of the MANGOMBE busbar (source side). <xref ref-type="fig" rid="fig1"><xref ref-type="fig" rid="fig">Figure </xref>1</xref>8(b) displays the contingency line voltage signal (single-phase short-circuit) before IPC compensation. Cancellation of phase A voltage (faulty phase) is observed. <xref ref-type="fig" rid="fig1"><xref ref-type="fig" rid="fig">Figure </xref>1</xref>8(c) displays the voltage signal at the output of the 1<sup>st</sup> IPC, and <xref ref-type="fig" rid="fig1"><xref ref-type="fig" rid="fig">Figure </xref>1</xref>8(d) displays the voltage signal at the output at the input of the 2<sup>nd</sup> IPC.</p><p><xref ref-type="fig" rid="fig1"><xref ref-type="fig" rid="fig">Figure </xref>1</xref>8(e) displays the load voltage signal at OYOMABANG in contingency (single-phase short circuit) after IPC compensation. It can be seen that after compensation of the RPIs, the pre-contingency values are found at the load.</p></sec><sec id="s3_10_2"><title>3.10.2. Intensity Samples</title><p><xref ref-type="fig" rid="fig1"><xref ref-type="fig" rid="fig">Figure </xref>1</xref>9(a) shows the intensity of current in line during the contingency, from where after opening of the phase A by the circuit breakers D1 and D4, the intensity of current becomes null. Then the two other phases are the seat of the energy transited between the two nodes of the network. The transmission line thus enters an unbalanced asymmetrical operation.</p><p>The source RPI will therefore perform forward, reverse, and zero-sequence compensation at the source. As well as the load RPI which will do the same thing on the load side. This thus makes it possible to cancel the inverse and homopolar component, and to raise the positive sequence component of the system, and to find the pre-contingency values.</p><p><xref ref-type="fig" rid="fig">Figure </xref>shows the current to the load after compensation of the inverse sequence, <xref ref-type="fig" rid="fig1"><xref ref-type="fig" rid="fig">Figure </xref>1</xref> shows the homopolar current which goes to ground.</p><p><xref ref-type="fig" rid="fig">Figure </xref>shows the current at the load after complete compensation by the two IPCs.</p><p>After this compensation, it appears that the voltage of the load returns to its pre-contingency value. The source and load currents have a slight difference between the amplitudes.</p></sec></sec><sec id="s3_11"><title>3.11. Simulation of the Contingency Line (Phase A and B)</title><p><xref ref-type="fig" rid="fig2"><xref ref-type="fig" rid="fig">Figure </xref>2</xref>0 presents the simulation of the line in contingency as well as the reconfiguration of the IPCs after a two-phase short-circuit. We also note the opening of the reactances which is not necessary for compensation. The compensation of the inverse sequence is carried out by the three reactances of phase A, the compensation of the direct sequence is carried out by the reactances X_CCs and X_CCr of the healthy phases. The results obtained in contingency are presented in <xref ref-type="fig" rid="fig2"><xref ref-type="fig" rid="fig">Figure </xref>2</xref>1 and <xref ref-type="fig" rid="fig2"><xref ref-type="fig" rid="fig">Figure </xref>2</xref>2 for a contingency on phase A and B.</p><p>Voltage samples.</p><p><xref ref-type="fig" rid="fig2"><xref ref-type="fig" rid="fig">Figure </xref>2</xref>1 displays the three-phase voltage signal at the MANGOMBE busbar (source side), as well as the voltage at OYOMABANG after compensation for the IPCs. There is a slight difference in the amplitudes of the contingency phases (A and B) with respect to the amplitudes of the source voltage.</p><p><xref ref-type="fig" rid="fig2"><xref ref-type="fig" rid="fig">Figure </xref>2</xref>2 shows the line current intensity during the contingency, hence after opening of phases A and B by the circuit breakers, the current intensity becomes zero on these phases. Then the healthy phase is the seat of the energy transited between the two nodes of the network. The transmission line thus enters an unbalanced asymmetrical operation.</p><p>The source RPI will therefore perform forward, reverse, and zero-sequence compensation at the source. As well as the load RPI which will do the same thing on the load side. This thus makes it possible to cancel the inverse and homopolar component, and to raise the positive sequence component of the system, and to find the pre-contingency values.</p><p>After this compensation, it appears that the voltage and the current have a slight difference between the amplitudes, compared to the pre-contingency value. The imbalance is not completely canceled.</p></sec></sec><sec id="s4"><title>4. Conclusions</title><p>The presented work shows the contribution of STATCOM and the interphase power controller in solving the problems encountered by the network manager. To achieve this, we first highlighted the particularities of the STATCOM and the IPC; then we carried out several simulation tests on the Mangombe-Oyomabang line in the presence of the STATCOM in symmetrical and asymmetrical operation, and then for the three-branch 240 duals IPC.</p><p>The simulation of the line in presence of STATCOM in asymmetrical operation allows us to note that in spite of the too important unbalance of the voltage at OYOMABANG. The STATCOM ensures a regulation by phase of the voltage regulation role, thus allowing to reduce the unbalance. The simulations of the line absence of defect in the presence of IPC 240 duals with three branches, made it possible to show that during this period the reactances of each IPC for the weak angles of load, adapt themselves to the variation of this angle.</p></sec><sec id="s5"><title>Conflicts of Interest</title><p>The authors declare no conflicts of interest regarding the publication of this paper.</p></sec><sec id="s6"><title>Cite this paper</title><p>Steva, K.C.C., Ghislain, M.M., Joseph, K.K., Jeannot, B.G. and Leandre,<sup> </sup>N.N. (2023) Contribution to Asymmetrical Compensation through Parallel Controllers of FACTS (STATCOM)—IPC 240 Dual for a Power Transmission Line. World Journal of Engineering and Technology, 11, 20-40. https://doi.org/10.4236/wjet.2023.111003<sup> </sup></p></sec></body><back><ref-list><title>References</title><ref id="scirp.122519-ref1"><label>1</label><mixed-citation publication-type="other" xlink:type="simple">Lilien, J.-L. (2009) Transport et distribution de l’énergie électrique. Course Given at the Institute of Electricity Montefiore University of Liege.</mixed-citation></ref><ref id="scirp.122519-ref2"><label>2</label><mixed-citation publication-type="other" xlink:type="simple">Ndjeng Ossono, E. (2014) Electricity in Cameroon: What Is the Way Forward? Denis &amp; Lenora Foretia Foundation, 11.</mixed-citation></ref><ref id="scirp.122519-ref3"><label>3</label><mixed-citation publication-type="other" xlink:type="simple">Sana, A.-R., McGillis, D., Marccau, R., Do, X. and Olivier, G. (2000) Asymmetrical Operation of Corridor with One Single Line. In 2000 Canadian Conference on Electrical and Computer Engineering. Navigating to a New Era (Cat. No. 00TH8492), 2, 936-940.</mixed-citation></ref><ref id="scirp.122519-ref4"><label>4</label><mixed-citation publication-type="other" xlink:type="simple">Steinmetz, C.P. (1916) Theory and Calculation of Alternating Current Phenomena. McGraw-Hill Book Company, Incorporated, New York.</mixed-citation></ref><ref id="scirp.122519-ref5"><label>5</label><mixed-citation publication-type="other" xlink:type="simple">Asma, B. and Soumia, D. (2019) Control of an SSSC by Neural Networks to Improve the Static Behavior of an Electroenergetic System. Master Thesis, University Ziane Achour of Djelfa, Djelfa.</mixed-citation></ref><ref id="scirp.122519-ref6"><label>6</label><mixed-citation publication-type="other" xlink:type="simple">Brochu, J., Pelletier, P., Beauregard, F. and Morin, G. (1994) The Interphase Power Controller: A New Concept for Managing Power Flow within AC Networks, IEEE Transactions on Power Delivery, 9, 833-841. https://doi.org/10.1109/61.296264</mixed-citation></ref><ref id="scirp.122519-ref7"><label>7</label><mixed-citation publication-type="other" xlink:type="simple">Léandre, N.N., Koko, J., Ndjakomo Essiane, S. and Batassou Guilzia, J. (2021) Comparative Analysis of Hybrid Controllers of FACTS Systems (UPFC) and Interphase Power Controllers Type RPI 30P15 on the Management of Electrical Network Contingencies. World Journal of Engineering and Technology, 9, 708-726.</mixed-citation></ref><ref id="scirp.122519-ref8"><label>8</label><mixed-citation publication-type="other" xlink:type="simple">Oldeen, J. and Sharma, V. (2020) Reinforcement Learning for Grid Voltage Stability with FACTS. Degree of Master, Uppsala University.</mixed-citation></ref><ref id="scirp.122519-ref9"><label>9</label><mixed-citation publication-type="other" xlink:type="simple">Kom, C.H., Mandeng, J.-J. (2020) Understanding Interphase Power Controller: A Description. Journal of Electrical Engineering, Electronics, Control and Computer Science, 6, 19-24.</mixed-citation></ref><ref id="scirp.122519-ref10"><label>10</label><mixed-citation publication-type="other" xlink:type="simple">Grunbaum, R., Noroozian, M., and Thorvaldsson, B.J.A.R. (1999) FACTS—Power- ful Systems for Flexible Power Transmission. ABB Review, No. 5, 4-17.</mixed-citation></ref><ref id="scirp.122519-ref11"><label>11</label><mixed-citation publication-type="other" xlink:type="simple">Shahraki, E.G. (2003) Apport de l’UPFC à l’amélioration de la stabilité transitoire des réseaux électriques. PhD Thesis, Université Henri Poincaré-Nancy 1.</mixed-citation></ref></ref-list></back></article>